Raritan PX Power Cord Installation Guide 

PowerCord_InstallGuide_1B_3.6.10 

 255-80-6083-00 RoHS 

 
 
 
 

 

 

In all 3-phase products, L1 is phase A, L2 is phase B, L3 is 
phase C and N is neutral. 

 

If your PDU is inlet metered, such as PDU models PX2-1nnn 
and PX2-2nnn (where n is a number), you must pass each 
line cord wire through the correct CT in the correct 
direction. Each CT is labeled and contains a direction arrow.   
Push the ring terminal end of the line cord through the CT 
in the direction indicated by the arrow. For example, push 
the L1 line cord wire through the CT labeled L1 and then 
connect it to the L1 terminal block. 

 

 

For Raritan in-line monitors, where there is a one to one 
correspondence between plug and receptacle, maintain the 
same wire colors for inlet and outlet flexible cords. 

7.

 

Make final adjustments to the cable gland and verify the jacket 
of the flexible cord extends into the Raritan product. Hand 
tighten the gland nut and finish tightening with a torque 
wrench. Appropriate torque settings vary according to the 
cable gland size. 

Cable gland size 

Torque setting (N·m) 

M12x1.5 

0.7 to 0.9 

M16x1.5 

2.0 to 3.0 

M20x1.5 

2.7 to 4.0 

M25x1.5 

5.0 to 7.5 

M32x1.5 

7.5 to 10.0 

M40x1.5 

7.5 to 10.0 

M50x1.5 

7.5 to 10.0 

M63x1.5 

7.5 to 10.0 

Note: The cable gland size is marked on the cable gland body. 

After tightening, examine the flexible cord and cable gland for 
the following: 

 

Make sure you can see a few remaining threads between 
the cable gland body and cable gland nut. The gland nut 
must not bottom out on the gland body. 

 

Make sure the flexible cord does not move in the cable 
gland when it is twisted, pushed or pulled. 

8.

 

Re-install the PDU wiring access panel or in-line monitor cover 
plate. This completes internal wiring of the Raritan product. 

9.

 

For in-line monitors, fasten the receptacles to the outlet 

flexible cords following the manufacturer’s instructions.

 

10.

 

Complete the wiring of the inlet flexible cord by performing one 
of these steps: 

 

Assemble the plug following the manufacturer’s 

instructions. 

 

Permanently attach and strain relief the flexible cord to a 
junction box following applicable electrical codes. 

 

Содержание PX2

Страница 1: ...eptacle Unplug a device connected to this product before performing repair maintenance or service on the device Failure to unplug a device before servicing it may result in electric shock fire personal injury and death WARNING Only use this product to power information technology equipment that has a UL IEC 60950 1 or equivalent rating Attempting to power non rated devices may result in electric s...

Страница 2: ...onitors on page 3 for exceptions If a plug is to be attached to the flexible cord the length of the flexible cord must not exceed 4 5 meters as specified in UL 60950 1 2007 and NEC 645 5 2011 The flexible cord may be permanently connected to power subject to local regulatory agency approval In the United States relevant electrical regulations can be found in NEC 2011 sections 400 7 A 8 400 7 B 368...

Страница 3: ...r Unused Channels It is not necessary to wire up all channels of multi channel in line monitors The inlet and outlet openings of unused channels must be completely closed off Goof plugs for this purpose may be a good choice if they are available in your country or region Step by Step Flexible Cord Installation The following items are required to complete the installation Flexible cord s Insulated ...

Страница 4: ...dels especially in line monitors the flexible cord s diameter may be too small for the cable gland A sealing ring for smaller diameter line cords may have been included with the Raritan product or can be requested from Raritan to reduce the inside diameter of the cable gland 5 Fasten the ring terminal of the green or green yellow ground wire to the chassis s threaded ground stud in this order a Pl...

Страница 5: ...a torque wrench Appropriate torque settings vary according to the cable gland size Cable gland size Torque setting N m M12x1 5 0 7 to 0 9 M16x1 5 2 0 to 3 0 M20x1 5 2 7 to 4 0 M25x1 5 5 0 to 7 5 M32x1 5 7 5 to 10 0 M40x1 5 7 5 to 10 0 M50x1 5 7 5 to 10 0 M63x1 5 7 5 to 10 0 Note The cable gland size is marked on the cable gland body After tightening examine the flexible cord and cable gland for th...

Отзывы: