Raritan PX Power Cord Installation Guide 

PowerCord_InstallGuide_1B_3.6.10 

 255-80-6083-00 RoHS 

 
 
 
 

 

Number 

Description 

 

Inlets (labeled LINE) 

 

Outlets (labeled LOAD) 

2.

 

Strip off the outer jacket of the flexible cord and remove any 
jute, paper or other fillers. Use the following to help determine 
how much jacket to remove: 

 

In the finished assembly, the outer jacket should protrude 
inside the Raritan product. 

 

The wires will have ring terminals crimped onto them. 

 

In the finished assembly, the wires should have some slack 
and not be taught. 

 

In the finished assembly, if the flexible cord slips in the 

cable gland placing a strain on the cord’s wires, the ground 

wire must be the last wire to take the strain. 

3.

 

Crimp an insulated ring terminal onto each wire. A 
non-insulated ring terminal may be used for the ground wire. 
Inspect each crimp to insure it is secure and verify no exposed 
wire protrudes from the rear of an insulated ring terminal. 

4.

 

Loosen the cable gland nut and push the flexible cord assembly 
through the gland. 

 

Temporarily hand tighten the gland nut and verify the cord 
cannot be twisted or pushed or pulled in the gland. Do not 
proceed if hand tightening results in a loose cord. In some 
models, especially in-

line monitors, the flexible cord’s 

diameter may be too small for the cable gland. A sealing ring 
for smaller diameter line cords may have been included with 
the Raritan product, or can be requested from Raritan, to 
reduce the inside diameter of the cable gland. 

 

5.

 

Fasten the ring terminal of the green (or green/yellow) ground 

wire to the chassis’s threaded ground stud in this order:

 

a.

 

Place the lock washer on the stud. 

b.

 

Place the ground wire ring terminal on the stud. 

c.

 

Place the nut on the stud and tighten with a torque wrench. 
The appropriate torque settings vary according to the nut 
size. 

Nut size 

Torque setting (N·m) 

Tolerance 

M3 

0.49 

10% 

M4 

1.27 

8% 

M5 

1.96 

5% 

M6 

2.94 

3.5% 

M8 

4.9 

2% 

d.

 

Check the ground wire connection. It should be secure and 
not move or rotate. 

 

6.

 

Fasten the ring terminals of all remaining wires to the terminal 
block and tighten each using a torque screwdriver. The 
appropriate torque settings vary according to the screw size. 

Screw size 

Torque setting (N·m) 

Tolerance 

M3 

0.49 

10% 

M4 

1.27 

8% 

M5 

1.96 

5% 

M6 

2.94 

3.5% 

M8 

4.9 

2% 

Make sure each ring terminal is firmly fastened and cannot be 
twisted by hand. Use the following guidelines to help terminal 
block wiring. 

 

In single-phase Raritan products with world-wide ratings, 
the terminals are labeled L1 and L2. L1 is the phase wire. L2 
is either the neutral (120/230V installations) or another 
phase wire (208V installations). 

 

Содержание PX2

Страница 1: ...eptacle Unplug a device connected to this product before performing repair maintenance or service on the device Failure to unplug a device before servicing it may result in electric shock fire personal injury and death WARNING Only use this product to power information technology equipment that has a UL IEC 60950 1 or equivalent rating Attempting to power non rated devices may result in electric s...

Страница 2: ...onitors on page 3 for exceptions If a plug is to be attached to the flexible cord the length of the flexible cord must not exceed 4 5 meters as specified in UL 60950 1 2007 and NEC 645 5 2011 The flexible cord may be permanently connected to power subject to local regulatory agency approval In the United States relevant electrical regulations can be found in NEC 2011 sections 400 7 A 8 400 7 B 368...

Страница 3: ...r Unused Channels It is not necessary to wire up all channels of multi channel in line monitors The inlet and outlet openings of unused channels must be completely closed off Goof plugs for this purpose may be a good choice if they are available in your country or region Step by Step Flexible Cord Installation The following items are required to complete the installation Flexible cord s Insulated ...

Страница 4: ...dels especially in line monitors the flexible cord s diameter may be too small for the cable gland A sealing ring for smaller diameter line cords may have been included with the Raritan product or can be requested from Raritan to reduce the inside diameter of the cable gland 5 Fasten the ring terminal of the green or green yellow ground wire to the chassis s threaded ground stud in this order a Pl...

Страница 5: ...a torque wrench Appropriate torque settings vary according to the cable gland size Cable gland size Torque setting N m M12x1 5 0 7 to 0 9 M16x1 5 2 0 to 3 0 M20x1 5 2 7 to 4 0 M25x1 5 5 0 to 7 5 M32x1 5 7 5 to 10 0 M40x1 5 7 5 to 10 0 M50x1 5 7 5 to 10 0 M63x1 5 7 5 to 10 0 Note The cable gland size is marked on the cable gland body After tightening examine the flexible cord and cable gland for th...

Отзывы: