Cycle function
Only available in EXPERT mode
For cyclical switch commands the switching on time is set by logical “OR“ of programs of all types. A fixed cycle of ON and OFF time then ope-
rates within those limits. The cycle always starts with the ON time.
The cycle duration and the ON time within the cycle are the same length for all switching times. The cycle duration and the ON time can be set
independently in one-second increments. If the switching time is shorter than the cycle duration, the cycle will be shortened accordingly. The
ON time will remain unchanged. If the switching time is actually shorter than the ON time, the ON time will be shortened accordingly.
0:10:00
0:10:00
0:10:00
0:04:00
0:04:00
0:04:00
15:00:00
15:10:00
15:20:00
15:30:00
15:32:00
Program 1
Relais Chanal 1
Program n
min
max
Period
2s
2h
Pulse
1s
1h 59min 59s
1
2
+
Switch off the device before dismantling the module. Do not switch on again until the module has been installed.
Always use a Li cell type battery (LiMnO
2
) CR2477, 3V, high temperature type min +70°C.