Over SNMP communication, battery test can be started or current test can be cancelled. UPS can be shut-
down or stand-by (stand-by duration is adjustable). Alarms can be discarded.
If Serial Communication cable is needed, it can be produced
according to the pin configuration described at side.
If the jumpers are at the upper side for internal SNMP configuration, RS232 and
RS485 Serial Communication are disabled.
If the jumpers are at the lower side for RS232 or RS485 configuration, internal SNMP
is disabled.
SNMP Jumper (J2 – J3):
If internal
SNMP would be used, 2 jumpers
should be moved to upper side.
If RS232 or RS485 would be used, 2
jumpers should be moved to lower
side.
6.2.
Internal SNMP Communication
Internal SNMP card can be installed into SNMP slot placed at the front of UPS. As soon as SNMP
installed, RS232 port would be disabled.
Internal SNMP has the same features as External SNMP; refer to Section 8.1 for more information.
SNMP RS232 - RS485
SNMP
SNMP
RS232
RS485
RS232
RS485
J2
J2
J3
J3
Содержание KEOR T
Страница 1: ...KEOR T Installation Manual LE07544AA ...
Страница 2: ...2 KEOR T ENGLISH 6 EN ...
Страница 5: ...5 KEOR T Installation Manual Battery Fast Fuses Installation Operating Manuals ...
Страница 32: ...32 Figure 5 3 1 4 1 Keor T 10 30kVA 1x60pcs 7 9Ah BATTERY WIRING DIAGRAM ...
Страница 33: ...33 KEOR T Installation Manual Figure 5 3 1 4 2 Keor T 10 30kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM ...
Страница 34: ...34 Figure 5 3 1 4 3 Keor T 40 60kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM ...
Страница 35: ...35 KEOR T Installation Manual Figure 5 3 1 4 4 Keor T 40 60kVA 3x60pcs 7 9Ah BATTERY WIRING DIAGRAM ...
Страница 50: ...50 SEPARATED RECTIFIER AND BYPASS INPUTS ...
Страница 51: ...51 KEOR T Installation Manual COMMON RECTIFIER AND BYPASS INPUTS ...