• Drawings S1 and S2 mean the bypass input acceptable window. For 3kVA; it can be 176VAC~264VAC or
187VAC~264VAC. For 6-10kVA; it can be 184VAC~260VAC or 195VAC~260VAC.
• Drawing T means the bypass frequency window of the Inverter Output, the acceptable setting values are
±3Hz and ±1Hz.
• Drawing U means the acceptable Inverter Output Voltage, of which voltage is 200VAC, 208VAC,
220VAC, 230VAC, or 240VAC.
• Drawing V1, V2, V3 and V4 mean the operation modes of the UPS, of which alternative is Online,
Eco(Economic) mode, fixed 50Hz Output or fixed 60Hz Output.
• Drawing W means the adjustments of the Inverter Output, which may be calibrated as 0%, +1%, 1%, +2%,
-2%, +3%, or -3%.
For only 6-10kVA;
• Drawing X means a specified address & position of the UPS when the UPS is in Parallel mode. The settable
numbers are from 1st to 4th. The number must be 1st if the UPS is not in parallel.
• Drawing Y means the parallel function status. The “P 01” means parallel function disabled and the “P02”
means parallel function enabled.
When all the setting changes are done, you have to press ENTER key Pad to save all the changes when
the LCD screen shows as drawing Z, then, the LCD screen will show as drawing AA tocomplete the setting
changes. Those changes will be activated only when the UPS is re-turned on.
If you don’t want to change those settings, you may press “OFF” key pads for 5 seconds, then the LCD
screen turns to Drawing AA directly, which means your setting changes are invalid.
OFF
* Please press Enter key to save data.
* It shows the UPS is locked.
Turn Off the breaker of Input. Your Setting changes are completed.