12
4.2.
Placement
• UPS is not designed for outdoor application.
• The equipment and the batteries should not be exposed to direct sunlight or placed near to a heat source.
• Recommended operating temperature and humidity values are listed on the
Appendix-3 Technical
Specifications section. To provide the required environmental condition.
• Avoid dusty environments or areas where dust of conductive or corrosive materials is present.
• The connection and the circuit breakers are at the back side of UPS. Leave at least 30 cm at the back side
of the UPS for maintenance.
• Air outlets of the UPS are present on the front and back sides. Leave at least 30 cm at the front and back
side of the UPS for ventilation.
• To eliminate any overheating of the UPS, keep all ventilation openings free from obstruction, and do not
store “things” on top of the UPS.
• Even though the operating temperature of the UPS and batteries are between 0-40 °C, It is suggested to
provide an environment temperature between 20-25°C to get maximum performance from the UPS and
batteries.
• Advised environmental humidity condition is between 30%~90% (non-condensing).
The UPS must be placed and stand in a vertical position throughout the transportation.
Use suitable equipment to remove the UPS from the pallet.
The equipment shall be packed properly during transportation. Therefore it is
recommended to keep the original package for future need.
Optimal battery life time is reached when battery ambient temperature is kept
between 15°C and 25°C. Operating battery at 30°C ambient temperature compared
to 20°C will divide by factor 2 battery life time. Room thermal management as
specified above is then necessary to avoid battery life time reduction. The Battery
warranty does not apply if the temperature in the room exceeds 25°C.
All packing material must be recycled in compliance with the laws in force in the
country where the system is installed.
4.1.
Transportation
4. Requirement