9 Technical features

MODEL 

ITEM

3 101 54

3 101 55

3 101 56

3 101 57

3 101 58

3 101 59

Output

Overload

Capacity

(tolerance 

+/-1%)

Line 

mode

<105% continuous

106-120% for 30 seconds 

121-150% for 10 seconds

>150% Immediately transfer to bypass.

Buzzer continuously alarms.

Battery 

mode

<105% continuous

106-120% for 30 seconds

121-150% for 10 seconds

>150% Immediately shuts down. 

Buzzer continuously alarms.

Bypass 

mode

<105% continuous

106-120% for 250 seconds shuts down 

121-130% for 125 seconds shuts down

131-135% for 50 seconds shuts down

136-145% for 20 seconds shuts down

Buzzer continuously alarms.

Efficiency

Line mode

90%

Battery mode

85%

ECO mode

96%

Battery

Battery type

12 V/7.2 Ah Sealed, non-spillage, 

maintenance-free, lead acid

Number of batteries

2

4

6

Rated Battery Voltage

24 VDC

48 VDC

72 VDC

Backup  

time

(Half  

Load)

PF=0.7

> 8 min

>9 min

> 10 min

Содержание KEOR LP

Страница 1: ...LP 1 2 3 kVA EN Index 1 Introduction 26 2 Condition of use 26 3 LED Panel 28 4 Rear Panel 30 5 Installation 31 6 Functions and Signal 34 7 UPS software 39 8 Possible malfunctioning 40 9 Technical feat...

Страница 2: ...UPS does not electrically isolate the internal parts To isolate your UPS unplug it from the mains power socket Do not open the UPS container since there may be parts inside with dangerously high volta...

Страница 3: ...Do not plug laser printers into the UPS because of their high start up current Do not plug house electric equipments such as hair dryer air conditioner and refrigerator into the UPS outlets Always swi...

Страница 4: ...Switch Press and hold until the buzzer beeps Self Test 1 2 a Commands the UPS to perform self testing Press and hold until the buzzer beeps b Battery Load Test Mode Do not hold for 1 second Manual By...

Страница 5: ...indicates LED Panel in Error Code Function Mode Overload LED 1 2 1 Indicates UPS is overloaded 2 In Error Code Mode indicates Error Code 16 Site wiring fault LED 1 2 1 Indicates live and neutral lines...

Страница 6: ...5 External battery connector 6 AC outlets 7 Utility input circuit breaker 8 AC power connection socket 9 Output circuit breaker for two outlets 4 Rear panel 1 2 3 6 1 2 3 6 5 1 7 8 4 1 2 3 6 8 7 5 9 4...

Страница 7: ...UPS while it is still in the plastic bag and check for the following standard package contents 5 Installation 1000 2000VA Schucko French IEC 320 C14 3000VA Schucko French IEC 320 C20 9 8 7 6 9 8 7 6...

Страница 8: ...ound To enable the EPO function short pins 1 and 2 Proceed to the installation as follows Please read the condition of use contained in this manual before installing the UPS Start Normal AC mode 1 Bef...

Страница 9: ...ress When the self test is completed the UPS will return to AC mode If there were no faults or abnormal conditions then the 1 2 and 1 2 LEDs will turn off Note the main function of self testing is to...

Страница 10: ...Bank of stationary maintenance free batteries 5 DC to DC push pull converter control circuit 6 Static bypass loop 7 Input and output EMI filters UPS Status Beep Code UPS faulty Inverter shut down All...

Страница 11: ...EDs Normal Working power starts after approximately 5 seconds LEDs on the panel will blink and fans will start Press the ON button 1 2 for 1 5 seconds The UPS starts up normally 1 2 LED ON 1 2 LED ON...

Страница 12: ...l turn on the AC DC converter turn off the DC DC converter and switch the charger to charging mode This is the same operating mode as in Figure 5 2 3 During a utility outage the UPS will work as illus...

Страница 13: ...e until the load is less than 105 Then the UPS will switch back to Inverter mode automatically 2 The UPS Bypass loop is also equipped with overload protection Its overload capacity is illustrated by t...

Страница 14: ...ult 1 2 will shine The UPS will cut off supply to the loads Inverter Current or Voltage Out of Tolerance If the UPS inverter delivers over current or out of tolerance voltage to its outlets then the U...

Страница 15: ...UPS software This software can be used for the following functions Automatic shutdown of the local computer UPS parameters reading Connection It is possible to to use RS 232 communication Connect a m...

Страница 16: ...obstructing the ventilation louvers Verify that the cooling fans are working properly Contact your local dealer to replace the fans if necessary 4 Site wiring Ground fault 1 2 4 Check if the L and N...

Страница 17: ...l receptacle or if the cord plug is faulty 1 Do not use the power strip 2 Replace the wall receptacle cord plug Strange noise or smell Immediately shut down the whole system Disconnect the power from...

Страница 18: ...oad LED 1 2 Each LED represents a number as shown in the figure below For example if the 25 50 and 100 bar LEDs are lit the error code is therefore 8 2 1 11 or Er11 which indicates that the UPS is ove...

Страница 19: ...gle phase with ground Power Factor 0 98 with full linear load Generator Input Supported Input Connection 10 A IEC 320 C14 16A IEC 320 C20 Output Voltage 230 V Voltage Regulation within 1 until low bat...

Страница 20: ...r 10 seconds 150 Immediately shuts down Buzzer continuously alarms Bypass mode 105 continuous 106 120 for 250 seconds shuts down 121 130 for 125 seconds shuts down 131 135 for 50 seconds shuts down 13...

Страница 21: ...tton ON Alarm Silence OFF Test Level Button Audible Alarm Battery Mode Sounds once every 1 5 seconds Low Battery Sounds once every 0 2 seconds Overload Sounds once every 3 seconds Normal alarm Sounds...

Страница 22: ...x444 322 189 444 Weight 10kg 16 5kg 22 5kg Environmental OperatingTemperature 0 40 C Noise Level 50 dBA Relative Humidity 0 90 without condensation Interface Interface Type RS 232 EPO Slots Dry conta...

Отзывы: