INSTALLATION INSTRUCTIONS

MRIMAS_F-3166_012918

Electrical Connection

9.  Mount and wire the MRIPSF-480 external power supply system per the procedures provided in the 

supplementary instruction sheet. Run conduit and DC wiring to an MRI room EMI filter. Make sure wiring is 
completely enclosed in grounded aluminum conduit. Any gaps, regardless of size, must be closed or wrapped in 
copper foil tape.

10. If a 0-10V dimming circuit is to be connected, install at this time. The 0-10V dimmer must be installed outside 

the shielded MRI environment with the Kenall MRIFD-1A dimming line filter (or equivalent) installed in 
accordance with the supplied installation instructions. Kenall recommends the Lutron Diva (DVSTV) and Lutron 
Nova T (NTSTV-DV) series to ensure the full range of dimming can be achieved. Contact Kenall for suitability in 
using an alternate sink-type 0-10V dimmer. Reattach the reflector / wireway with the screws that were removed 
in step 3.

WARNING: All DC power and dimming signal wiring must be run through separate EMI filters.
11. After the luminaires are mounted and secured, access the internal junction box to gain access to supply 

connections. Each wire is labeled and color coded for easy identification.

Figure 4

Tray Removal

Figure 3

Reflector   Removal

Figure 5

Mounting Holes

Figure 6

Supply Wire and Mounting Hole Locations

Содержание Kenall MRIMAS Series

Страница 1: ... sheet applies for the MRI MedMaster Auracyl Sconce MRIMAS Series A separate instruction sheet is provided in the MRIPSF 480 external power supply system Both sheets are intended to provide comprehensive instructions on fixture installation and wiring The MRI MedMaster Sconce lighting system contains sensitive electronics Take care to avoid damage by improper handling or static electricity dischar...

Страница 2: ... closed or wrapped in copper foil tape 10 If a 0 10V dimming circuit is to be connected install at this time The 0 10V dimmer must be installed outside the shielded MRI environment with the Kenall MRIFD 1A dimming line filter or equivalent installed in accordance with the supplied installation instructions Kenall recommends the Lutron Diva DVSTV and Lutron Nova T NTSTV DV series to ensure the full...

Страница 3: ... or wrapped in copper foil tape Special attention should be paid to the wiring entry point into the shielded space Class 1 wiring methods are required 13 Run the dimming signal wiring equal in specification to the filter input wiring between the filter output cables and the first luminaire within the shielded room Maintain polarity between input and output sides of the filter and follow wiring rec...

Страница 4: ...w kenall com Resources Certified Performance Warranties WARRANTY Figure 8 Standard Luminaire Screw Detail Conclusion of Luminaire Mounting Procedure 19 Reattach the LED tray F to the baseplate C 20 Reattach the reflector wireway with the screws that were removed in step 3 21 Hook the front housing B onto the angle bracket hook D shown in Figure 8 22 Replace the screw s removed in step 1 NOTE Do no...

Отзывы: