INSTALLATION INSTRUCTIONS
F-5419
6. When installing exit light (provided with battery
for emergency operation) connect battery leads to
terminals identified on driver board. Connect red
lead to terminal (positive) and black lead
to terminal marked – (negative).
7. Install electrical gear into housing and secure with
attachment screws.
8. Attach the sign panel by compressing the torsion
springs and inserting them into the slots on the
electrical gear plate.
9. Check installation by gently pulling on housing and
canopy to ensure it is securely held in place.
10. Energize AC supply, LED display will illuminate.
11. When provided with battery, charge battery for 24
hrs. prior to building occupancy.
II. CEILING PENDANT MOUNT
1. De-energize the circuit at the junction box (J-box)
where the exit sign is to be installed.
2. Extend unswitched 24 hour AC supply of rated
voltage from the junction box of sufficient length
to allow for routing into electrical housing.
3. Route wires through the center hole of mounting
plate and securely fasten the mounting plate to the
J-box with screws.
4. Remove center knock out of electrical housing for
attachment of mounting stem. Attach opposite
end of stem to canopy.
5. Route the wires through the canopy/pendant and
mount the canopy over the mounting plate with
supplied mounting hardware.
6. Attach electrical gear to the electrical housing
with supplied hardware. Connect power supply
accordance with local codes. Wire connections as
follows: Line to Black lead; Neutral to White lead.
Connect green grounding lead to supply grounding
conductor.
7. When installing exit light (provided with battery
for emergency operation) connect battery leads to
terminals identified on driver board. Connect red
lead to terminal (positive) and black lead
to terminal
marked – (negative).
8. Install electrical gear into housing and secure with
attachment screws.
9. Attach the sign panel by compressing the torsion
springs and inserting them into the slots on the
electrical
gear plate.
10. Check installation by gently pulling on housing and
canopy to ensure it is securely held in place.
11. Energize AC supply, LED display will illuminate.
12. When provided with battery, charge battery for 24
hrs. prior to building occupancy.