49
EN
4. Few seconds after the second key confirmation, the UPS turns on in stored energy mode and the
loads are powered. The alarm LED
and the green LEDs
light up. It is audible
an intermittent sound alarm.
The display looks like the following figure:
5. The start-up procedure is completed. If the UPS is not plugged to the mains outlet, the loads are
powered till the end of the backup time.
INDICATION
The output frequency is the same that there was at the input before the UPS was shutdown. The
default value is 50 Hz but if before the UPS shutdown the input frequency was 60 Hz, then the
output frequency after the cold start will be 60 Hz.
4.4
Shutdown
1. Press and hold
until the buzzer sounds twice.
2. The UPS stops powering the loads and turns to the standby mode. The green LEDs
switch off. The ventilating fans continue spinning.
3. Unplug the UPS from the wall receptacle if there is still input voltage. After 10 seconds, the fans
stop working and the UPS completely shuts down.
4.5
UPS Measurements
After the UPS is turned on, it is possible to check the UPS measurements by pressing
or
.
DAKER DK Plus
1 kVA - 3 kVA
The display sequence is:
- AC input voltage
and current
;
- AC input frequency;
- output voltage;
- output frequency;
- load percentage;
- output current;
- battery voltage;
- battery autonomy;
- UPS internal temperature;
- battery status
,
real and apparent power
.
Содержание DAKER DK Plus Series
Страница 1: ...DAKER DK Plus 1 kVA 3 kVA Manuel d installation Installation manual ...
Страница 7: ...38 3 Installation 3 1 Package content Check for the following package content ...
Страница 8: ...EN 39 3 2 Tower configuration setup 3 2 1 UPS DAKER DK Plus 1 kVA 3 kVA ...
Страница 9: ...40 3 2 2 UPS battery cabinet optional 3 Installation S1 ...
Страница 11: ...42 3 Installation ...