UPS user manual
Manuel de l’utilisateur de l’ASI
Utilizzo dell’UPS
16
OMG38225 REV. F
When the
Green Conversion
algorithm is active the rectifier operates at reduced DC voltage and supplies
the inverter alone, since the battery is disconnected from the DC bus. The battery charge is controlled by
a specific algorithm. In case no mains outage events have occurred, and so no battery discharges have
occurred too, the control logic provides to start a charging cycle once every 25 days. The battery-charger
restores the capacity lost due to the self-discharge and remains in floating charge for additional 12 hours.
As this time has elapsed the battery static switch is opened and the battery is disconnected from the DC
bus.
In case a discharge event occurs, the control logic provides to calculate the capacity which has been lost
during the discharge; as the mains is restored a charging cycle is started, which is extended for an
additional time that depends on the percentage of lost capacity, referred to the rated value.
Lost capacity < 10%
Additional charge for
12 hours
Lost capacity between 10% and 20%
Additional charge for
48 hours
Lost capacity > 20%
Additional charge for
96 hours
Such values complies with the recommendations of the main battery manufacturers.
Set the right battery capacity
The UPS front panel allows the setting of the battery parameters, including the rated
capacity. Considering the importance that such value assumes for the correct execution
of the charge control algorithm, it is highly recommended to verify the correctness of the
programmed value.
3.3.3 Bypass
operation
The load can be switched to bypass either automatically or manually. The manual changeover is due to
the BYPASS SWITCH which forces the load to bypass. In case of failure of the bypass line, the load is
switched back to inverter without interruption.
Picture 4 – Load supplied by bypass
3.3.4 Battery
operation
In case of power failure or rectifier fault, the battery feeds the inverter without interruption. The battery
voltage drops based on the amplitude of the discharging current. The voltage drop has no effect on the
output voltage, which is kept constant by changing the PWM modulation. An alarm is activated when the
battery is near the minimum discharge value.
In case the supply is restored before the battery is completely discharged, the system will be switched
back to normal operation automatically. In the opposite case, the inverter shuts down and the load is
Содержание BSK93
Страница 1: ...UPS OPERATING MANUAL MANUEL DE FONCTIONNEMENT DE L ASI MANUALE OPERATIVO UPS KEOR HPE 60 160 kVA ...
Страница 3: ......
Страница 5: ......
Страница 175: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMG38225 REV F 9 ENGLISH LANGUAGE ...
Страница 176: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 10 OMG38225 REV F ...
Страница 226: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 60 OMG38225 REV F LANGUE FRANÇAIS ...
Страница 277: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMG38225 REV F 111 LINGUA ITALIANA ...
Страница 278: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 112 OMG38225 REV F ...
Страница 328: ...UPS OPERATING MANUAL MANUEL DE FONCTIONNEMENT DE L UPS MANUALE OPERATIVO UPS KEOR HPE 200 250 300 kVA ...
Страница 330: ......
Страница 497: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMP06263 REV B 11 ENGLISH LANGUAGE ...
Страница 551: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMP06263 REV B 65 LANGUE FRANÇAIS ...
Страница 605: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMP06263 REV B 119 LINGUA ITALIANA ...
Страница 644: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 158 OMP06263 REV B ...
Страница 660: ...UPS OPERATING MANUAL MANUEL DE FONCTIONNEMENT DE L UPS MANUALE OPERATIVO UPS KEOR HPE 400 500 kVA ...
Страница 662: ......
Страница 829: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMP06263 REV B 11 ENGLISH LANGUAGE ...
Страница 883: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMP06263 REV B 65 LANGUE FRANÇAIS ...
Страница 937: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMP06263 REV B 119 LINGUA ITALIANA ...
Страница 976: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 158 OMP06263 REV B ...
Страница 992: ...UPS OPERATING MANUAL MANUEL DE FONCTIONNEMENT DE L ASI MANUALE OPERATIVO UPS KEOR HPE 60 80 kVA ...
Страница 994: ......
Страница 996: ......
Страница 1234: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMW07104 REV A 9 ENGLISH LANGUAGE ...
Страница 1235: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 10 OMW07104 REV A ...
Страница 1284: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMW07104 REV A 59 LANGUE FRANÇAIS ...
Страница 1286: ......
Страница 1336: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMW07104 REV A 111 LINGUA ITALIANA ...
Страница 1337: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 112 OMW07104 REV A ...
Страница 1387: ...THREE PHASE UPS From 60 to 500 kW Keor HPE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES ...
Страница 1397: ...11 WWW UPS LEGRAND COM UPS CONVENTIONAL UPS ...