5/38
Cat. No(s).: 5 735 04/05
5 735 12/13
KNX
Arteor 4 and 6 touches glass controls
Technical data sheet: S000090563EN-2
Updated: 07/06/2016
Created : 27/07/2015
7. OPERATION (continued)
7.1.2 Additional functions (continued)
Possible action
Send
incremented
commands
(by scrolling)
• Successive short presses: send incremented
commands.
The chosen commands are sent one after the other
(incrementation or decrementation between a min. and
max. value, between 0 and 255)
Example: 1st press: comfort (command 1), 2nd press:
standby (command 2), 3rd press: eco (command 3), 4th
press: comfort (command 1)
Double action
send (send
2 commands)
This function is used to associate products that do not
have the scenario function with a scenario
Conditional send
Mode 1/Mode 2
When pressed, sends a command or a second different
command, according to a condition.
The control can manage different circuits according to
an event.
Example: in a meeting room, one press activates the
switch-on of the 4 luminaires (mode 1).
When a mobile partition is used in this meeting room,
one press activates the 2 luminaires on the corridor side
of the room.
Clean mode
This function allows to disable the touch plate during
cleaning (10").
Press short
Short press
Send
commands
Send
double
action
Send conditional
Mode 1 or Mode 2
Short
press
Press 4:
comfort
Press 3:
eco
Press 1:
comfort
Press 2:
standby
…
Mode 2
With mobile partition
Meeting room
Mode 1
Without partition
7.2 Operation of the LEDs
Each control has a number of configurable RGB LEDs (4 to 6 depending
on the Cat. No.) which indicate, for each press, the status of the system
using the colours, flashing and brightness of the LEDs.
When the control has not yet been programmed, all the LEDs change
colour quickly.
• Choice of 12 colours: green, blue, white, orange, gold, yellow,
turquoise, cyan, light blue, purple, magenta, crimson
• Choice of LED behaviour: on continuously or various types of flashing
Key:
LED goes off
LED blinks slowly
LED blinks quickly
LED flashes
• Choice of the brightness of the LEDs (0 to 100%)
• Default modes:
ON = steady green
Off = steady blue
Alarm = blinking red (cannot be modified)
Control deactivated = steady orange
• Physical address programming mode: steady red LEDs
7.2.1 Setting the brightness
- Normal brightness: adjustable value
- Eco brightness: adjustable value
- Standby brightness: value cannot be adjusted (off)
The LED's lights up at maximum brightness level for 30s after pressing
any push button.
The brightness setting will be the same for all the LEDs on the control
7.2.2 Setting the colour and behaviour
• Actuator status feedback: ON or OFF
• System status feedback: contextual information indicated via the BUS
Example: over-consumption, broken lamp, too much wind for roller
blinds.
It is also possible to use the control in pilot light mode.