Automatic transfer switch
4 226 81
Installa
tion and user manual
11
6. Password access
The ATS has a password function that at first switching on is not active in order to access to all parameters (M03
Password OFF).
N.B. In case of password activation/modify, it is recommended to make a copy of it to guarantee future ac-
cess with desired privileges.
• It is possible to define different level of password in order to permit different access to “
settings/commands
” menu in
function of access privileges.
• If password is activated, in order to enter to protected data, it is necessary to insert the correct code.
• To enable password management and to define numeric codes, see M03
“password
” menu.
• There are different access levels:
• Password disabled (OFF)– The password is disabled. Complete access to all parameters (Default Legrand).
• Password enabled (ON) – The password is enabled:
- Access without to insert password (Lev.1) The password is enabled but not inserted. This access allow the visual-
ization only.
- User Level access (Lev.2) It allows the change of mode, the clearing of recorded values and editing of a limited
number of setup parameters.
- Advance Level access (Lev.3) Complete access to all parameters.
MENU
Password OFF
Password ON (liv2-liv.3)
NO Password Lev 1
Lev. 2
Lev. 3
M01
●
X
●
●
M02
●
X
X
●
M03
●
X
X
●
M04
●
X
X
●
M05
●
X
●
●
M06
●
X
●
●
M07
●
X
X
●
M08
●
X
X
●
M09
●
X
X
●
• The default password for each level are the followings:
Password mode
Password OFF default Legrand
Full Access
Password ON
Level
Password
1
-
2
1000
3
2000
• From normal viewing, press
to recall main menu, select the password icon and press
.
The display shows the screen below:
•
Fig. 13 - Enter password
Fig. 14 - Enter password level Ok
Fig. 15 - Enter Wrong password level
With keys
▲
and
▼
it is possible to change the selected digit.
• With keys +
◄
and -
►
it is possible move through the digits.
ATTENTION! To confirm the password it is mandatory to select
icon and to confirm with
OK.
If the code is confirmed with OK without going on key icon “
”, the value won’t be accepted.
• In function of level password “Level 2-
User or Level 3-Advanced”
the correspondent unlock message is shown.
• Once unlocked the password, the access rights are valid until one of the followings conditions are verified:
- A timeout period of two minutes elapses without any keystroke.
- The device is reset (after quitting the setup menu).
- The device is turned off.
• To quit the password entry screen press
key.