8.1. Serial Communication (RS232)
UPS is equipped with Serial Communication as standard. RS232 cable shall be shielded and shorter than 25m.
RS232:
DSUB-9 male connector with the following pin layout shall be used on the UPS side of the connection cable.
The communication solutions listed below can be used with this port:
•
Monitoring Software (Optional)
•
External SNMP Adapter (Optional)
Via SNMP; the information listed below can be monitored;
The Latest Battery Test Date
UPS Information (example: 220V - 50Hz)
Input Data (V
in
, F
in
, V
max
vb.)
Output Data (V
out
, Load Percantge...etc.)
Battery Situation (V
batt
...etc)
RS232 PIN LAYOUT
PIN#
Signal Name
Signal Description
2
RX
Receive Data
3
TX
Transmit Data
5
GND
Signal Ground
Tablo.8
Communication Cable Path
Figure.8-2
Содержание 30 KVA
Страница 1: ...KEOR T 10 60 KVA INSTALLATION MANUAL ...
Страница 4: ...IV Installation Operating Manuals Battery Fast Fuses ...
Страница 30: ...25 KEOR T 10 30kVA 1x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 1 ...
Страница 31: ...26 KEOR T 10 30kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 2 ...
Страница 32: ...27 KEOR T 40 60kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 3 ...
Страница 33: ...28 KEOR T 40 60kVA 3x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 4 ...
Страница 46: ...41 Appendix 3 Description of UPS and Block Diagram SEPARATED RECTIFIER AND BYPASS INPUTS ...
Страница 47: ...42 COMMON RECTIFIER AND BYPASS INPUTS ...