4. REQUIREMENT
4.1. Transportation
4.2. Placement
This product meets the safety requirements for devices to be operated in restricted access locations according to EN
60950-1 safety standard, which states that the owner should guarantee the following:
•
Access to the equipment can only be gained by service persons or by users who have been instructed about the
reasons for the restrictions applied to the location and about any precautions that shall be taken and,
•
Access is through the use of a tool or lock and key, or other means of security and is controlled by the authority
responsible for the location.
•
UPS is not designed for outdoor application.
•
The equipment and the batteries should not be exposed to direct sunlight or placed near to a heat source.
•
Recommended operating temperature and humidity values are listed on the
Appendix-1 Technical Specifications
.
•
Avoid dusty environments or areas where dust of conductive or corrosive materials is present.
•
The connection and the circuit breakers are at the front of UPS. Leave access at the front of the UPS for
maintenance. (Refer to Figure.4.2-3)
•
Air outlets of the UPS are at the front, back and on both sides. Leave access at the front side, back side and from
both lateral sides for ventilation and battery replacement. (Refer to Figure.4.2-1, 4.2-2 and 4.2.-3)
•
Recommended environmental humidity condition is between 20-95% (non-condensing).
Environment Requirement
Model (kVA)
10
15
20
30
40
60
Max. dissipation at full load
(W)
470
705
940
1410
1880
2820
(BTU)
1604
2406
3207
4811
6415
9622
Storage temperatures
-25/+55 °C (-13/131 °F) (15-25 °C for maximum battery life)
Working temperature
0/40 °C (32/104 °F) (15-25 °C for maximum battery life)
Maximum relative humidity
95% max. without condensation
Maximum altitude without derating
1.000 m (3.300 ft)
Degree of protection
IP 20 (other IP as option)
Colour cabinet
RAL 7016@enclosure RAL 9005@front door metal
Table.1
The UPS must be placed and stand in a vertical position throughout the transportation.
Use suitable equipment to remove the UPS from the pallet.
The equipment shall be packed properly during transportation. Therefore it is recommended to keep
the original package for future need.
All packing material must be recycled in compliance with the laws in force in the country where the
system is installed.
Optimal battery life time is reached when battery ambient temperature is kept between 15°C and
25°C. Operating battery at 30°C ambient temperature compared to 20°C will divide by factor 2 battery
life time. Room thermal management as specified above is then necessary to avoid battery life time
reduction. The Battery warranty does not apply if the temperature in the room exceeds 25°C.
Содержание 30 KVA
Страница 1: ...KEOR T 10 60 KVA INSTALLATION MANUAL ...
Страница 4: ...IV Installation Operating Manuals Battery Fast Fuses ...
Страница 30: ...25 KEOR T 10 30kVA 1x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 1 ...
Страница 31: ...26 KEOR T 10 30kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 2 ...
Страница 32: ...27 KEOR T 40 60kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 3 ...
Страница 33: ...28 KEOR T 40 60kVA 3x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 4 ...
Страница 46: ...41 Appendix 3 Description of UPS and Block Diagram SEPARATED RECTIFIER AND BYPASS INPUTS ...
Страница 47: ...42 COMMON RECTIFIER AND BYPASS INPUTS ...