![LEGRAND 0 489 55 Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/legrand/0-489-55/0-489-55_manual_1871697002.webp)
2/9
Microwave detector - DALI/DSI dimming
Technical data sheet: S000105459EN-2
Updated: 25/02/2021
Created: 05/12/2018
Cat. No(s): 0 489 55/56/57
CONTENTS
2. TECHNICAL CHARACTERISTICS (CONTINUED)
3. DIMENSIONS
4. CONNECTION
Channel 1 (switched output) can either be used to switch a set of
luminaires, or to isolate the mains supply of DALI/DSI dimming ballasts
(saving on the standby consumption of the ballasts).
Multiple loads can be connected in parallel as long as the maximum
total load is not exceeded.
Channel 2 (dimmable output) can be used to dim DALI/DSI ballasts or
dimming transformers.
The ballasts/transformers can be connected in parallel as long as the
maximum number is not exceeded.
The wiring examples below show common installations using this
detector.
1 - Halogen lamps
2 - ELV halogen lamps with
separate ferromagnetic ballast
3 - Fluorescent tubes with separate
ferromagnetic ballast
4 - Compact fluorescent lamps with
separate ferromagnetic ballast
5 - ELV halogen lamps with
separate electronic ballast
6 - Fluorescent tubes with separate
electronic ballast
7 - Compact fluorescent lamps with
built-in electronic ballast
8 - Compact fluorescent lamps with
separate electronic ballast
9 - LED lamps with separate
electronic ballast
10 - LED lamps with built-in
electronic ballast
4. CONNECTION (CONTINUED)
Single channel dimming with manual dimming control
Single channel dimming with manual dimming control
Functions:
Switching the luminaire according to occupancy and
maintaining a defined lighting level. Override dimming and switching
using a centre-biased retractive switch.
Configured for presence detection:
Turns on automatically when
occupancy is detected. Maintains the lighting level. Press and release
the down button to turn off, press and release the up button to turn
back on. Press and hold the down button to dim down, press and hold
the up button to dim up. Turns off automatically when occupancy is no
longer detected.
Configured for absence detection:
Press and release the up button to
turn on. Maintains the lighting level. Press and release the down button
to turn off, press and release the up button to turn back on.
Press and hold the down button to dim down, press and hold the up
button to dim up. Turns off automatically when occupancy is no longer
detected.
Channel mode:
Set to “Switch and dim together”.
Manual control mode:
Set to “Synchronised 1-position push-button”.
230 V
A
10 A
10 A
10 A
10 A
10 A
230 V
A
10 A
10 A
10 A
10 A
10 A
Dimming
ballast
DIM-
N
L
L/OUT
DIM
SW1/UP
SW2
DOWN
Dimmable DSI or
DALI luminaire
230 V switching push-button
(for absence detection)
30 ballasts max
2
7
3
8
5
4
9
1
6