![LEGRAND 0 489 35 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/legrand/0-489-35/0-489-35_technical-data-manual_1870346005.webp)
5/8
Technical data sheet: S000088482EN-1
Updated:
Created: 02/01/2017
Cat. No(s): 0 489 35
PIR+US ceiling mount sensors
(DALI)
6.1 TEST function
6.2 Configuration
Configuration of a DALI installation is described in the
DALI programming
manual.
7. SETTINGS
7.1 Detection settings
Time delay:
Length of time the load is on after detection.
Pulse mode (= push-button mode)
: If the time delay is set to
0, the sensor is in push-button mode. In this case, there is a
10-minute time delay before the load is switched off. If the setting
is overridden or there is a new detection, the 10-minute time delay
starts again.
Possible with configuration tool 0 882 30/BMSO4001.
Sensitivity:
Detection range setting.
7.1 Detection settings (continued)
Auto on/Auto off mode:
The lighting switches on automatically:
- On detection of presence if the natural light level is insufficient
The lighting switches off automatically:
- Where no presence is detected and at the end of the time delay
set
- Or if the natural light level is sufficient (regulation activated)
Another detection causes automatic switch-on if there is
insufficient light.
Walkthrough mode:
- If no presence is detected in the 20 seconds following an initial
detection, the device will switch off the load after 3 minutes.
- If another movement is detected in the 3 minutes following
initial detection, the device will switch off the load at the end of
the set time delay.
Manual on/Auto off mode:
The lighting is switched on via a manual control, but switches off
automatically:
- Where no presence is detected and at the end of the time delay
set
After switch-off, if another movement is detected within a
30-second period, the lighting switches on automatically.
The Restart function must be enabled.
After 30 seconds, the lighting has to be switched on manually.
Detection system:
Initial detection:
The load is switched on as soon as the first detection
occurs if the natural light level is below the light level threshold.
Maintain:
The load remains active if another presence is detected.
Restart:
In manual mode. After switch-off, any new detection within a
30-second period triggers an automatic switch-on.
After 30 seconds the device must be switched on manually.
Possible in Manual on/Auto off mode only.
Alarm:
An audible signal is emitted before switch-off. 1 minute before,
then 30 seconds, then 10 seconds.
7.2 Light level settings
Daylight setpoint:
Value at which the load comes on if the natural
light level is less than the setting.
Eye function:
Value 0 (eye on configuration tool 0 882 30/BMSO4001)
is used to save the ambient light level in the room as a daylight
setpoint.
6. OPERATION
7. SETTINGS (
CONTINUED
)
Sensor settings
Default
value
Modifiable
parameters
Configuration
tools
0 882 30
BMSO4001
Time delay
15 min
5 s - 2 hrs
Sensitivity
PIR
(very high)
US (high)
Low, medium,
high, very high
Modes
Auto on/Auto off
Active
Enable/
Disable
Walkthrough
Inactive
Enable/
Disable
Manual on/
Auto off
Inactive
Enable/
Disable
Detection
system
Initial
PIR and US PIR and/or US,
PIR, US
Maintain
PIR or US
PIR and/or US,
PIR, US
Restart
PIR or US
PIR and/or US, PIR,
US/Disable
Alarm
Inactive
Enable/
Disable
Sensor settings
Default
value
Modifiable
parameters
Configuration
tools
0 882 30
BMSO4001
Daylight setpoint
500 lux
5 - 1275 lux
Advanced
mode
Calibration
−
0 - 99995 lux
Light regulation
Active
Enable/
Disable
Light
contribution
Auto
Auto - 1275 lux