PIR+US ceiling mount sensors

(DALI)

CONTENTS

 

6.1 TEST function

 

6.2 Configuration

Configuration of a DALI installation is described in the 

DALI programming 

manual.

7. SETTINGS

 

7.1 Detection settings

 

Time delay: 

Length of time the load is on after detection.

Pulse mode (= push-button mode)

: If the time delay is set to 

0, the sensor is in push-button mode. In this case, there is a 

10-minute time delay before the load is switched off. If the setting 

is overridden or there is a new detection, the 10-minute time delay 

starts again.

Possible with configuration tool 0 882 30/BMSO4001.

Sensitivity: 

Detection range setting.

 

7.1 Detection settings (continued)

 Auto on/Auto off mode: 

The lighting switches on automatically: 

- On detection of presence if the natural light level is insufficient
The lighting switches off automatically: 

- Where no presence is detected and at the end of the time delay 

set 

- Or if the natural light level is sufficient (regulation activated)
Another detection causes automatic switch-on if there is 

insufficient light.

Walkthrough mode: 

- If no presence is detected in the 20 seconds following an initial 

detection, the device will switch off the load after 3 minutes. 

- If another movement is detected in the 3 minutes following 

initial detection, the device will switch off the load at the end of 

the set time delay.

Manual on/Auto off mode: 

The lighting is switched on via a manual control, but switches off 

automatically: 

- Where no presence is detected and at the end of the time delay 

set

After switch-off, if another movement is detected within a 

30-second period, the lighting switches on automatically.  

The Restart function must be enabled.

After 30 seconds, the lighting has to be switched on manually.

Detection system:

Initial detection: 

The load is switched on as soon as the first detection 

occurs if the natural light level is below the light level threshold.

Maintain:

 The load remains active if another presence is detected.

Restart: 

In manual mode. After switch-off, any new detection within a 

30-second period triggers an automatic switch-on.
After 30 seconds the device must be switched on manually.
Possible in Manual on/Auto off mode only.

Alarm:

 An audible signal is emitted before switch-off. 1 minute before, 

then 30 seconds, then 10 seconds.

 

7.2 Light level settings

Daylight setpoint: 

Value at which the load comes on if the natural 

light level is less than the setting.

Eye function:

 

Value 0 (eye on configuration tool 0 882 30/BMSO4001) 

is used to save the ambient light level in the room as a daylight 

setpoint.

6. OPERATION

7. SETTINGS (

CONTINUED

)

Sensor settings

Default 

value

 

Modifiable 

parameters

 

 

Configuration 

tools

 

 

0 882 30

  

  

BMSO4001

Time delay

15 min

     

5 s - 2 hrs

    

    

Sensitivity

PIR  

(very high)

US (high)

Low, medium, 

high, very high

Modes

Auto on/Auto off

Active

Enable/

Disable

Walkthrough

Inactive

Enable/

Disable

Manual on/

Auto off

 

Inactive

Enable/

Disable

Detection

 

system

  

 

Initial

PIR and US PIR and/or US, 

PIR, US

Maintain

PIR or US

PIR and/or US, 

PIR, US

Restart

PIR or US

PIR and/or US, PIR, 

US/Disable

Alarm

Inactive

Enable/

Disable

Sensor settings

Default 

value

 

Modifiable 

parameters

 

 

Configuration 

tools

 

 

0 882 30

  

   

BMSO4001

Daylight setpoint

500 lux

  

5 - 1275 lux

 

Advanced 

mode

  

Calibration

 

0 - 99995 lux

Light regulation

Active

Enable/

Disable

Light 

contribution

 

Auto

Auto - 1275 lux

Содержание 0 489 35

Страница 1: ...roups are made up as follows 2 window and corridor groups which can be used to dim the lighting for which it is possible to set a light level offset and a display board group which can only be switche...

Страница 2: ...t No s 0 489 35 PIR US ceiling mount sensors DALI CONTENTS 3 1 Sensor location 3 2 Recommended light exposure 3 INSTALLATION US PIR 2 5 m 1 5 m 3 3 Mounting 3 4 Recommended light exposure 3 5 Removal...

Страница 3: ...ensors DALI CONTENTS 4 DIMENSIONS 50 58 50 1 2 2 5 1 Wiring with a single sensor 5 CONNECTION D 5 2 Wiring with several sensors 5 CONNECTION CONTINUED D x 64 max 0 488 72 Cat Nos 0 035 13 15 200 mA ma...

Страница 4: ...be connected to a master sensor via Cat No 048878 150m max D D 100 m 0 5 mm2 150 m 0 75 mm2 300 m 1 5 mm2 25 mA 2 mA 5 4 Wiring with several sensors one control unit and a DALI unit Cat No 0 488 76 D...

Страница 5: ...ch off if another movement is detected within a 30 second period the lighting switches on automatically The Restart function must be enabled After 30 seconds the lighting has to be switched on manuall...

Страница 6: ...ly possible if the installation includes a DALI unit Cat No 0 488 76 The lighting is only switched on when presence is detected and can be switched off with a push button Master Slave parameter settin...

Страница 7: ...5 6 25 3 5 5 25 6 5 35 4 6 5 35 7 5 45 5 6 30 10 5 90 6 4 15 5 5 25 High sensitivity 75 Very high sensitivity 100 m surface m2 m surface m2 Height m 2 5 6 5 30 8 50 3 8 5 60 11 5 100 4 12 5 125 14 155...

Страница 8: ...h light provided Enable the regulation function Reduce the daylight setpoint Decrease the power of the luminaires Time delay too short Detection sensitivity too low Daylight setpoint too low Increase...

Отзывы: