background image

25

Installation of bends in the outlet vent pipe

If there is a requirement for installing bends in the outlet air pipe in 
order to pass around a window or a protruding part of the roof (see 
fig. 9), the following should be observed:

• 

If the pipe is installed at an angle of 30 degrees, the total length of 

the angled part of the pipe must not exceed 1.5 m.

• 

If the pipe is installed at an angle of 45 degrees, the total length of 

the angled part of the pipe must not exceed 1.0 m.

If bends are installed, a maximum of two 45 degree bends or two 30 
degree bends may be used. Note: The maximum total length of the 
pipe may not exceed 4.5 m when any bends are installed.

6. FINAL INSTALLATION

Install the required fittings. If the outlet pipe is installed up a wall, fit-
tings for attaching the pipe to the wall may be required.

The enclosed T-piece should always be used. The plug installed in the 
T-piece must always be located at the underside since there is an exit 
hole for moisture on the underside of the T-piece.
Because of this, the T-piece should not be enclosed, as it is necessary 
to inspect the exit hole to make sure it is not blocked by leaves or  
similar objects. In cases where T-pieces must be enclosed, an  
inspection hatch must be installed.

A bowl can be placed under the internal T-piece for the collection of 
any moisture.
Push the enclosed ventilator cowl onto the pipe until it stops.

NOTE:

 Do not install a mosquito net over the end of the outlet air pipe.

Cinderella may be secured to the floor using suitable fixings - see fig. 
10.

Electric power

Connect the mains plug to an earthed socket. The mains supply 
voltage must be 230 V and minimum a 10 A fuse. Make sure the 
circuit has sufficient capacity. If you need information about rules and 
regulations related to the electric installation, you should have a word 
with a qualified electrician.

Installing an outlet air pipe through the ceiling

Cut an 80 mm long piece off the short pipe (NOTE: Not at the bevelled 
end). Draw a line 35 mm from the bevelled end of the pipe (see fig. 8), 
lubricate the end with dishwashing detergent or a similar substance, 
push the bevelled end of the pipe into the Cinderella then attach the  
T-piece to this pipe.

Place the Cinderella on the floor area selected for installation. Mea-
sure vertically from the centre of the vertical T-pipe to the  centre of 
the spot in the external roof where the pipe will be fed through. Cut 
a hole with a 111 mm hole saw. Repeat the procedure through the 
ceiling and ensure that the pipe is properly fed through the ceiling/
roof. If the outlet air pipe is to be enclosed (for example using metal 
cladding), make sure that the end of the pipe extends at least 400 mm 
above the enclosure. Make sure that the pipe is fed through the roof 
in compliance with building regulations. If you are unsure, contact a 
qualified tradesman.

fig. 8

fig. 9

In order to attach Cinderella to the floor: 
Remove the ash container. Drill holes 
through the indicated mounting holes. 
Use appropriate wooden screws or  
machine screws as appropriate to the floor 
material. 

fig. 10

If Cinderella is incorrectly 
installed, the user’s gua-
rantee will be voided.

Содержание Cinderella Comfort

Страница 1: ...INSTALLASJON y INSTALLATION y ASENNUSOHJE CINDERELLA COMFORT...

Страница 2: ...ash container to the steel frame 3 Remove plastic straps Transport safety strap Inlet air Outlet air Proper installation long service life Installing your Cinderella Comfort correctly has a num ber o...

Страница 3: ...air is provided from inside the room which must have a separate air vent of at least 160 mm diameter The outlet pipe is routed either inside the toilet or through and up an out side wall This alternat...

Страница 4: ...nimal back pressure If the vent pipe is to be enclosed using metal plating etc the end of the pipe must extend at least 400 mm above the enclosure see fig 1 Before cutting any holes you must ensure th...

Страница 5: ...ipe should be pushed 4 After determining the correct length and location of the inlet air pipe cut the pipe on the outside NOTE Cut the pipe flush with the external wall see fig 4 The inlet air pipe s...

Страница 6: ...hole saw Install the enclosed short air pipe through the wall with the bevelled end towards the Cinderella see fig 7 Make a mark 35 mm from the bevelled end of the pipe to indicate how far the pipe sh...

Страница 7: ...rella may be secured to the floor using suitable fixings see fig 10 Electric power Connect the mains plug to an earthed socket The mains supply voltage must be 230 V and minimum a 10 A fuse Make sure...

Страница 8: ......

Отзывы: