Installation of bends in the outlet vent pipe
If there is a requirement for installing bends in the outlet air pipe in
order to pass around a window or a protruding part of the roof (see
fig. 9), the following should be observed:
•
If the pipe is installed at an angle of 30 degrees, the total length of
the angled part of the pipe must not exceed 1.5 m.
•
If the pipe is installed at an angle of 45 degrees, the total length of
the angled part of the pipe must not exceed 1.0 m.
If bends are installed, a maximum of two 45 degree bends or two 30
degree bends may be used. Note: The maximum total length of the
pipe may not exceed 4.5 m when any bends are installed.
6. FINAL INSTALLATION
Install the required fittings. If the outlet pipe is installed up a wall, fit-
tings for attaching the pipe to the wall may be required.
The enclosed T-piece should always be used. The plug installed in the
T-piece must always be located at the underside since there is an exit
hole for moisture on the underside of the T-piece.
Because of this, the T-piece should not be enclosed, as it is necessary
to inspect the exit hole to make sure it is not blocked by leaves or
similar objects. In cases where T-pieces must be enclosed, an
inspection hatch must be installed.
A bowl can be placed under the internal T-piece for the collection of
any moisture.
Push the enclosed ventilator cowl onto the pipe until it stops.
NOTE:
Do not install a mosquito net over the end of the outlet air pipe.
Cinderella may be secured to the floor using suitable fixings - see fig.
10.
Electric power
Connect the mains plug to an earthed socket. The mains supply
voltage must be 230 V and minimum a 10 A fuse. Make sure the
circuit has sufficient capacity. If you need information about rules and
regulations related to the electric installation, you should have a word
with a qualified electrician.
Installing an outlet air pipe through the ceiling
Cut an 80 mm long piece off the short pipe (NOTE: Not at the bevelled
end). Draw a line 35 mm from the bevelled end of the pipe (see fig. 8),
lubricate the end with dishwashing detergent or a similar substance,
push the bevelled end of the pipe into the Cinderella then attach the
T-piece to this pipe.
Place the Cinderella on the floor area selected for installation. Mea-
sure vertically from the centre of the vertical T-pipe to the centre of
the spot in the external roof where the pipe will be fed through. Cut
a hole with a 111 mm hole saw. Repeat the procedure through the
ceiling and ensure that the pipe is properly fed through the ceiling/
roof. If the outlet air pipe is to be enclosed (for example using metal
cladding), make sure that the end of the pipe extends at least 400 mm
above the enclosure. Make sure that the pipe is fed through the roof
in compliance with building regulations. If you are unsure, contact a
qualified tradesman.
fig. 8
fig. 9
In order to attach Cinderella to the floor:
Remove the ash container. Drill holes
through the indicated mounting holes.
Use appropriate wooden screws or
machine screws as appropriate to the floor
material.
fig. 10
If Cinderella is incorrectly
installed, the user’s gua-
rantee will be voided.