
16 Channel Automatic Matrix Mixer
SERIAL PORT COMMANDS AVAILABLE
All LecNet devices use a modification of the typical one-to-one connection between two RS-232 compatible devices.
LecNet devices have both an RS-232 transmitter and receiver section. The transmitter section is “tri-stated”, or
placed in a high impedance mode, until the particular device is addressed. To facilitate the simple parallel connec
tion of multiple devices on a single RS-232 port, an addressing scheme is employed to route commands from the
host to the proper LecNet device. When a device receives its address from the host computer, it temporarily turns on
its RS-232 transmitter long enough to send whatever data is requested by the host. In this way, multiple devices may
drive a single transmit signal back to the host, because only the addressed device will turn on its transmitter.
Valid address values are 128-254 (80 hex-FE hex). Address 255 (FF hex) is reserved and must not be used. Be
cause a LecNet device will interpret any single data byte whose value is greater than 127 as an address, single byte
data (as opposed to addresses) sent from the host must be in the range of 0-127. If a data value needs to be sent
from the host that exceeds 127, the host must format two bytes of output such that the first byte is the lower 7 bits of
the 8 bit value, and the second byte is 1 if the MSB of the data byte is 1, or 0 if the MSB of the data byte is 0.
All interchange of commands and data with any LecNet device should be done in hex rather than ASCII. The only
exception to this is the return data on the Get Device Name command (see command description below).
Each LecNet command must be preceded by the address of the device to be controlled. If a device with the re
quested address exists on the system, it will respond by sending a 0 (0 hex, not ASCII) back to the host. Some
serial controller devices may simply send commands and data to a LecNet device and have no need to receive data.
In this case, step 2 below is replaced by a minimum 25 millisecond wait. This wait is necessary to insure that the
addressed LecNet device is “listening” and can respond to the command. Thus, each interchange with a LecNet
device follows this pattern:
1) Host sends device address in hex (1 byte);
2) Host receives byte of 0 hex from the LecNet device as acknowledgment;
3) Host sends command (1 byte, hex) to the LecNet device;
4) Host and LecNet device exchange data based on particular command sent.
Note that some LecNet commands cause LecNet devices to return an additional acknowledgment byte of data to
confirm the end of a transaction. This is most typical of commands that cause the LecNet device to be busy for more
than a few milliseconds processing the command. The additional acknowledgment byte lets the host know that the
LecNet device is no longer busy and can receive more commands. If a command does return an additional acknowl
edgment byte, this will be explicitly stated in the command description.
As an example of a specific interchange between a host and an AM16/12 the following general procedure would be
used to get a name string back from an AM16/12:
Set up the communications parameters of the device which will be the host. The correct parameters for all LecNet
devices are 9600 baud, no parity, 8 data bits, 1 stop bit. This must only be done once when the host is initialized.
1) Host sends device address. For a factory default AM16/12, this would be 139, or 8B hex (1 byte);
2) Host receives byte of 0 hex from the AM16/12 as acknowledgment;
3) Host sends command 1 hex (1 byte) to the AM16/12 to get the name data;
4) The LecNet device sends to the host 7 bytes. The first byte is 6 hex, which is the number of bytes in the
AM16/12’s name string. The AM16/12 will then send the ASCII characters “A”, “M”, “1”, “6” , “1” and “2” to
the host.
The following section is a listing of available commands grouped based on the AM16/12 function to which the com
mands are related. The word “Host” in the command descriptions means the IBM PC or compatible, AMX controller,
or Crestron controller to which the AM16/12 is connected. If you are using an AMX system to control your LecNet
equipment, you’ll want to purchase the Lectrosonics PT3 Protocol Translator. The PT3 connects between the AMX
bus and any LecNet equipment. With the PT3, the LecNet equipment behaves like native AMX equipment. The PT3
is the fastest and most productive way to control LecNet devices with an AMX system. Crestron has macros avail
able on their website for Lectrosonics equipment at http://www.crestron.com.
The following commands are described from the perspective of the host. A “Get” command allows the host to
receive information from the AM16/12. A “Set” command allows the host to send information to set some parameter
in the AM16/12. All commands and data have both the decimal values and hex values noted in the command
description.
Rio Rancho, NM – USA
29