26
ENGLISH
Terminal7 -
230 Vac motor M2 power supply phase (closure)
Terminal8 -
230 Vac motor M2 power supply phase (opening)
Note
: connect the capacitor of the motor M2 between terminals 8 and 7
Terminal board J6
Terminal1 –
Electric lock 12 Vac power supply
Terminal2 –
Electric lock 12 Vac and 24 Vac power supply (common)
Terminal3 –
24Vac power supply for photo-cells or other devices
Terminal4 –
M1 Opening limit switch normally closed electric contact
Terminal5 –
M1
Closing limit switch normally closed electric contact
Terminal6 –
M2 Opening limit switch normally closed electric contact
Terminal7 –
M2
Closing limit switch normally closed electric contact
Terminal8 –
Common terminal for all electric contacts of limit switches
Terminal9 –
Pedestrian start push-button’s normally open electric contact
Terminal10 –
Photo-cell normally closed electric contact
Terminal11 –
Emergency push-button’s normally closed electric contact (stop)
Terminal12 –
Start push-button’s normally open electric contact
Terminal13 –
Common terminal for all electric contacts of commands or security devices
Important: The normally closed inputs not in use must be fitted with jumpers
Terminal14
–
2nd radio-channel’s normally open electric contact (output)
Terminal15
–
2nd radio-channel’s normally open electric contact (output)
Terminal board J6
Terminal1 –
Aerial cable connection (shield) for radio receiver card
Terminal2 –
Aerial cable connection (signal) for radio receiver card
Connector J3
Terminal1 –
230 Vac mains power supply neutral
Terminal2 –
230 Vac motors M1 and M2 Power supply common
Terminal3
– 230 Vac motors M1 and M2 Power supply common
Terminal4 –
230 Vac motors M1 and M2 Power supply common
Important: If the power regulator card is not connected the J3 connector’s terminals 1 and 2 must be bridged with 4 mm insulated faston