5
I I . O v e r v i e w
CellarPro Cooling Capacity*
Estimated thermal loads for various size cellars, with various insulations, various
ambient temperatures and various cellar temperatures, are shown in the table below.
To figure out whether a CellarPro unit will work in your space, make sure that the
cooling unit’s BTUH for a given cellar temperature (at the top of the table) is equal or
greater than the thermal load shown in the body of the table. The non-bold,
unshaded numbers are within the capacity of all units. The unbold, lightly shaded
numbers are within all units except the 1800QTL. The bold numbers are beyond the
capacity of the 1800QTL and 1800QT. The italicized numbers are appropriate only
for the 1800XTS / XTSx. “X” indicates conditions beyond the capacity of all units.
Cellar Temp
55 Degrees
60 Degrees
BTUH
1800QTL
1065
1154
BTUH
1800QT
1380
1479
BTUH
1800XT
1456
1558
BTUH
1800XTS / XTSx
1886
2031
Cellar Insulation –
Walls, ceiling & floor*:
R-12
R-19
R-12
R-19
Cellar Size
Ambient Temp
75 Degrees
1068
979
940
862
100 Cu Ft.
85 Degrees
1180
1046
1038
920
95 Degrees
1291
1114
1136
980
75 Degrees
1380
1253
1214
1103
200 Cu Ft.
85 Degrees
1538
1349
1353
1187
95 Degrees
1699
1446
1495
1272
75 Degrees
1700
1542
1496
1357
300 Cu Ft.
85 Degrees
X
1562
1672
1463
95 Degrees
X
1909
2003
1558
75 Degrees
X
1744
1690
1535
400 Cu Ft.
85 Degrees
X
1879
1888
1654
95 Degrees
X
X
X
1773
*Please note: Glass panels, windows and doors have much lower insulation (at most
R-3) and therefore heat loads will increase dramatically when glass is used in cellars.