       Installation guide 

Local Control Network

2

Hinweise:

 

!

Keep distances to power supplies!  The connecting cable (I-port extension) between

!

an LCN-IVH/-IV  to  another LCN-IV´s  is a signal line. 

!

If the LCN-IVH/-IV is being used as an impulse sensor, no other groups may be   

connected to the I-port  (except the impulse generator.) 

!

Connect NO external voltages to the LCN-IV!

!

The terminal “GND” on the LCN-IV is on the N potential of the connected  LCN module.

!

The I-port extension should be carried out using a shielded cable. The shielding is not to 

be connectedt!

!

If the LCN-IV is being used as an impulse counter, the cable to the impulse contact 

should be as short as possible. An extension is possible (max. 50m) when using two   
LCN-IVH/-IV´s.

Guidelines to I-port connections:

The I-connecting cable to the LCN module can be extended up to a maximum of 50m with 
an LCN-IV  (all diverted distances added together), use  

³

0,8mm

Æ

 .

The distance from the LCN-NUI to a maximum of  2  GT-key sensors, must not be longer 
that  20m.  Only a maximum of five I-port  periphery devices may be connected.

Please  see also  ”TDi  connections from  peripheries” on www.LCN.de