background image

75.5319.00   20080111 

 

Page 7 of 9 

 

 

 

 

 
 
 
 
 

 
 
 
 
 
 

 

 
 
 
     
 
 
 
 

 
 

 

 

 
 

 
 

 

Manual Setup

 

 

 

 

If a remote control is not available, only the sensitivity parameter can be adjusted manually, by means of the push  
buttons 

+ (Plus) 

and

  - (Minus).

 

 
 
The sensor parameters that are not accessible manually will remain at the factory preset values.   

 
 

                                  

 

 
 

 

Pressing the two push buttons located on the circuit board, simultaneously for at least two seconds, will 
restore all default values except the lock code. Previously set lock codes will be retained. 

 
 

 

 
 

 
 
 

+

  Press to increase 

sensitivity by one unit. 

-

 

Press to decrease  

sensitivity by one unit.

 

 

Immunity 

 

Immunity helps to reduce the chance of 
unwanted detections due to environmental 
disturbances. 
 
1 = Reduced 
= Normal 
= Increased 
4 through 9: enhanced immunity (for highly  
 reflective environment) 
Default: 

 

 

Relay Hold Time

 

 

Relay hold time refers to the hold time on the 
output relay of the Eagle. Values range from 0 to 
9. 
 
= .5 sec. 
= 1 sec through = 9 sec in 1 second intervals 
 
Default: 0

 

 

 

Detection Mode

 

 

 

 

Detection mode offers 3 different levels of 
detection: 
 
1 = Bi-Directional 
2 = Uni-Directional 
= Uni-Directional with motion tracking feature 
 
Default: 

 

 

 

 
 

 

Sensitivity 

 

 

 

 

0 = Minimum Sensitivity 
9 = Maximum Sensitivity 
 
Default: 

* Every adjustment, when using the infrared remote control, must start with the unlocking function, and end with the  
   locking function.  

Содержание 8310-854

Страница 1: ...y Max contact voltage Max contact current Max switching power 60 VDC 125 VAC 1A resistive 30W DC 60VA AC Hold time 0 5 sec to 9 sec adjustable Temperature range 4 F to 131 F Dimensions 4 75in W x 3 15...

Страница 2: ...e can build up on the human body and then discharge when you touch a board A discharge can be produced when walking across a carpet and touching a board for example Before handling any board make sure...

Страница 3: ...wn in the picture Drill as instructed Pass the cable where indicated 4 Electrical Installation Terminal Connection 1 Red 12 to 24 VAC DC 2 Black 12 to 24 VAC DC 3 White Relay Common 4 Green Relay NO 5...

Страница 4: ...SENSING FIELDS ACCORDING TO THE VERTICAL TILT ANGLE OF THE ANTENNA The sensing fields on the right correspond to the following adjustments wide sensing field antenna vertical angle of the antenna 0 20...

Страница 5: ...E THE DIMENSIONS WIDTH DEPTH OF THE SENSING FIELD DEPEND ON THE MOUNTING HEIGHT The sensing fields on the right correspond to the following adjustments Wide sensing field antenna Vertical angle of th...

Страница 6: ...seconds following the last detection of motion toward the door At the end of the 2 second time frame if the sensor does not detect any further motion it switches back to the unidirectional mode Unlock...

Страница 7: ...one unit Immunity Immunity helps to reduce the chance of unwanted detections due to environmental disturbances 1 Reduced 2 Normal 3 Increased 4 through 9 enhanced immunity for highly reflective enviro...

Страница 8: ...ry Switch to unidirectional mode without MTF and increase the immunity In airlock vestibules the sensor sees the opposite door Increase immunity In airlock vestibules the sensor sees the movement of t...

Страница 9: ...75 5319 00 20080111 Page 9 of 9 Appendix Wiring Diagrams...

Отзывы: