6 Technical Specifications
Model
Index
10kVA(33 mode)
15kVA(33 mode)
20/25kVA(33
mode)
In
p
u
t
Input mode
3φ4W+PE(can be set to 1φ2W+PE)
Voltage range (V)
176Vac
~
280Vac, for 100% load.
80Vac
~
176Vac, linear derating
Frequency range (Hz)
50/60±10(50/60 self-adaption)
Bypass synchronism track
range(Hz)
50/60±10%Hz
Bypass
input
voltage
range(V)
220/230/240±20% (phase voltage) (default is 220)
Input power factor
≥0.99
Input THDI
Resistive full load:≤3%; non-linear full load: ≤5%
Battery voltage(VDC)
+144~+240 (can be selected from +12 cells ~+20 cells, default is +16
cells, when the battery voltage is set from +12 cells ~+15 cells, the
output of the UPS decreases to 75% rated) (12V battery)
Charge current (A)
1~10A settable (default is 4A)
O
u
tp
u
t
Output mode
3φ4W+PE(can be set to 1φ2W+PE)
Capacity (kVA/kW)
10/9
15/13.5
20/18
Voltage (V)
L-N: 220/230/240(default is 220)