• POSITIONING OF THE CHIMNEY FOR INDOOR APPLICATION
Sometimes a chimney is necessary to remove the exhaustsfrom the
pressure cleaner.
This problem hasn’t to be faced when the machine operates outdoor,
but when it’s installed indoor, the following recommendations must be
followed:
- The chimney path must be always in ascent, straight vertical if possible,
and preferably not exceeding a 5 m
lenght.
- The exit of the chimney must be
sheltered to avoid the dripping of
rain and to allow the exaust flow.
- The chimney section A must be
3 times the outlet chimney of the
machine B and at distance of at
least 20 cm.
It must be underlined that the
above recommendations are
extremely important to prevent the
condensate from back dripping into
the machine. The exausts contain
sulphuric acid, condensating at a
temperature of approximately 180°
C. The condensation shall be avoid,
but in any case the condensate
from chimney shall not enter the
machine.
The non observance of these
recommendations may lead to the
damage of the machine.
CHIMNEY SECTION: 3 times the
area of chimney
Chimney pipe diameter = 150 mm
CHIMNEY SECTION FOR 2 BOILER:
6 times the area of chimney
Chimney pipe diameter = 225 mm
NO
NO
NON
NEIN
NO
NEE
NO
NO
NON
NEIN
NO
NEE
min. 120°
A = 2B
A
B
min. 20 cm
min. 7,9 inch
OK
OK