54
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
© Systeme Lauer GmbH
AEG250PX-Expander driver
○
○
○ ○ ○ ○ ○
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
○○
D
D1.1
Delimitation
The System Lauer operating consoles of the PCS topline series are designated in
the following as PCS. The parameterization software for parameterizing the PCS
is designated as PCSPRO.
The successful parameterization of the PCS, as described in the PCS 91/925/991
or 9091 manual, is assumed. This appendix relates exclusively to the use of a PCS
together with an A250 controller of the AEG company. This controller is defined in
the following as programmable controller, the programming software for the
programmable controller as DOLOG, and the DOLOG program to be loaded as
AEG250PX. The AEG-specific terms and the programming of the programmable
controller with the DOLOG software are assumed as known.
This driver was developed on the A250 controller.
The PCS is connected to the programming interface of the controller.
Warning!
Use only the PCSPROPCSPRO
WIN
/PCSPRO
PLUS
software and/or PCS 9092 for
the configuration. Other software packages can initiate malfunctions in the
PCS and programmable controller.
D1.2
Loading of the AEG250PX driver into the THE PCS
During configuration of the PCS, both the user program with data and a selected
driver are transferred. The driver is called AEG250PX.
To configure a PCS-MIDI set DIL 7 according to the required baud rate (OFF =
38.5 Kbaud, ON = 115 Kbaud), DIL 8 on OFF and DIL 9 on ON. Connect PCS
and PC via the PCS 733 programming cable. After you have selected the expander
driver for the AEG A250 in the PCSPRO or PCS9092 programming software, the
AEG250PX driver is loaded automatically. Before, you must inform the driver of the
location of the send and receive buffer in the programmable controller. The MW
1256 start flag is defined as default. Take note during configuration that the length
of the buffer is 100 words. If other values than the defaults are used, then the
variables in the AEG250PX programmable controller handling software must also
be adjusted correspondingly! This is described comprehensively in section 3.
First commissioning
D1. First commissioning