ICS-6-OEM Instruction Manual
01807-53-000
Page 13 of 32
Issue 5 19 January 2021
If there are two or more switches, connect the contacts in series as shown below.
The Emergency Stop input may be driven by volt-free isolated contacts from a PLC or safety relay if
desired. The contacts must both be closed for the system to operate and they should be arranged to
operate simultaneously to avoid being detected as mismatched by the ICS-6-OEM.
If an emergency stop is not used, a wire link must be fitted between the two ‘A’ terminals on the E
STOP terminal block, and a second wire link across the ‘B’ terminals.
Note:
The E-stop switch should be checked periodically.
6.2 ICS-6-OEM Illuminated Sign Control Output
Low Voltage DC Warning Signs
The following options are for 24VDC warning signs such as Lasermet’s Miniature and Ultra Warning
Signs. These signs must not be connected to the mains supply.
Option 1 – One Way Illuminated LED Warning Sign
The warning sign will come on when the controller is armed. One of the seven outputs of the ICS-6-
OEM is used to illuminate the sign. This output must not then be used to operate a laser interlock as
well.