Following steps required for installation -

1. Install unit’s mounting accessory per

instructions supplied with the mount.

2. Install unit’s pushbutton test station (purchased

separately) per instructions supplied with the

to provide a method of disconnection the supply 

source from the unit. An example of how this 

can be completed is shown in Fig.1 for typical 

installation.

3. Verify that the supply voltage available is 120V

thru 277V.

4. 

120V thru 277V 

operation from the factory.  Lamp provided with 

environment as follows: (A) Unscrew and 

remove the globe support assembly (B) from 

the unit tank (C).  Install lamp. Re-attach globe 

to the installed mount.  If 277V application is 

desired refer to step 5.

CAUTION

:  During installation or maintenance, 

care must be taken to avoid scratching, nicking 

or chipping the glass globe.

5. Make sure the external threads at the top of

 

the unit tank are free of any dirt, metal chips

 

or 

other foreign materials. Apply a thin coat of 

lubricant to the threads.

 

NOTE

: Take extreme 

care not to cross thread

 

the unit when installing 

into the mounting

 

accessory.  Install the unit by 

threading into

 

the mounting accessory; the 

electrical contacts

 

will automatically engage. Be 

sure the unit is

 

threaded tight. Tighten the set 

screw on the side

 

of the mounting accessory.

6. Energize unit and verify that proper charging of

charging indicator lamp inside of globe area is 

on.

7. Test emergency lamp operation by pressing

PUSH-TO-TEST pushbutton of test station and

observe that the lamp operates.

8. To install optional guard (E) loosen the four

screws on the bottom of the globe support ring,

slip the guard over the screws and rotate to the

NOTE

:  Emergency ballast must be charged for 

36 hrs before running test(s).

FIG.1

SEE REVERSE FOR 

TYPICAL TEST INSTALLATION 

FIG.1 AND FIG.2

Page 3 of 5

Содержание EXP-EMG-EXT-42W SERIES

Страница 1: ... recommendations contained in these documents is based upon information that Larson Electronics believes to be reliable All the information and advice contained in these documents is intended for use only by persons having been trained and possessing the requisite skill and know how and to be used by such persons only at their own discretion and risk The nature of these instructions is informative...

Страница 2: ...e battery The emergency ballast contains a sealed no maintenance battery Contact manufacturer for information on replacements Batteries must be recycled or disposed of properly service personnel The use of accessory equipment not recommended by the manufacturer can cause an unsafe condition Equipment should be mounted in locations and at heights were it will not readily be subjected to tampering b...

Страница 3: ...e glass globe 5 Make sure the external threads at the top of the unit tank are free of any dirt metal chips or other foreign materials Apply a thin coat of lubricant to the threads NOTE Take extreme care not to cross thread the unit when installing into the mounting accessory Install the unit by threading into the mounting accessory the electrical contacts will automatically engage Be sure the uni...

Страница 4: ...ted 2 Test operation of the circuit at 30 day intervals for a minimum of 30 seconds The lamp should operate 3 Conduct a 90 minute discharge test once a year The lamp should operate for 90 minutes CAUTION To reduce the risk of electrical shock disconnect the AC input and inverter before servicing TYPICAL TEST INSTALLATION FIG 3 SEE REVERSE FOR TEST MAINTENANCE RECORDS CHART Page 4 of 5 ...

Страница 5: ...VE ALL INSTRUCTIONS TEST MAINTENANCE RECORDS Unit Location and or Number ________________________________________________________ DATE TEST DURATION MAINTENANCE PERFORMED COMMENTS 30 min 1 hr Page 5 of 5 ...

Отзывы: