Following steps required for installation -
1. Install unit’s mounting accessory per
instructions supplied with the mount.
2. Install unit’s pushbutton test station (purchased
separately) per instructions supplied with the
to provide a method of disconnection the supply
source from the unit. An example of how this
can be completed is shown in Fig.1 for typical
installation.
3. Verify that the supply voltage available is 120V
thru 277V.
4.
120V thru 277V
operation from the factory. Lamp provided with
environment as follows: (A) Unscrew and
remove the globe support assembly (B) from
the unit tank (C). Install lamp. Re-attach globe
to the installed mount. If 277V application is
desired refer to step 5.
CAUTION
: During installation or maintenance,
care must be taken to avoid scratching, nicking
or chipping the glass globe.
5. Make sure the external threads at the top of
the unit tank are free of any dirt, metal chips
or
other foreign materials. Apply a thin coat of
lubricant to the threads.
NOTE
: Take extreme
care not to cross thread
the unit when installing
into the mounting
accessory. Install the unit by
threading into
the mounting accessory; the
electrical contacts
will automatically engage. Be
sure the unit is
threaded tight. Tighten the set
screw on the side
of the mounting accessory.
6. Energize unit and verify that proper charging of
charging indicator lamp inside of globe area is
on.
7. Test emergency lamp operation by pressing
PUSH-TO-TEST pushbutton of test station and
observe that the lamp operates.
8. To install optional guard (E) loosen the four
screws on the bottom of the globe support ring,
slip the guard over the screws and rotate to the
NOTE
: Emergency ballast must be charged for
36 hrs before running test(s).
FIG.1
SEE REVERSE FOR
TYPICAL TEST INSTALLATION
FIG.1 AND FIG.2