EPL-MJ-XXW-LED Series
Explosion Proof LED Jar Light
Instruction Manual
WARNING
TO AVOID THE RISK OF FIRE, EXPLOSION OR ELECTRIC SHOCK, THIS PRODUCT SHOULD BE INSTALLED,
INSPECTED AND MAINTAINED BY A QUALIFIED ELECTRICIAN ONLY, IN ACCORDANCE WITH ALL
APPLICABLE ELECTRICAL CODES.
TO AVOID ELECTRIC SHOCK:
•
BE CERTAIN ELECTRICAL POWER IS OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE.
•
PRODUCT MUST BE CONNECTED TO A WIRING SYSTEM WITH AN EQUIPMENT-GROUNDING
CONDUCTOR.
TO AVOID EXPLOSION:
•
MAKE SURE THE SUPPLY VOLTAGE IS WITHIN THE VOLTAGE RATING.
•
ENSURE THE MARKED T RATING IS LESS THAN THE IGNITION TEMPERATURE OF THE HAZARDOUS
ATMOSPHERE.
•
DO NOT OPERATE IN AMBIENT TEMPERATURES ABOVE THOSE INDICATED ON THE PRODUCT
NAMEPLATE.
•
DO NOT OPERATE IF THE LENS, CORD, SEALS, HOUSING, RECEPTACLES, ETC. IS CRACKED OR
DAMAGED. IF SO, DISCONTINUE USE AND CONTACT MANUFACTURER FOR REPLACEMENT PARTS.
•
ALL FASTENERS SHOULD BE PROPERLY SEATED.
The Larson Electronics Explosion Proof LED Jar Light provides operators with a powerful alternative to traditional hazardous
location luminaries, including metal halide, high pressure sodium, mercury vapor, halogen, CFL and incandescent lamps.
This LED unit carries an IP67 waterproof rating and features an extended lifespan of 75,000+ hours. Compatible with ceiling,
wall, and pendant mount installations, the mason jar style fixture is field serviceable and features pyramid light distribution
that closely resembles traditional bulbs.
Larson Electronics, LLC
Phone: (877) 348-9680
Fax: (903) 498-3364
www.larsonelectronics.com
1
of
2
Mounting
The EPL-MJ series LED light fixture is available with several
different mounting configurations, specified when ordering. Find
your chosen mount configuration below for specifics:
Pendant:
Pendant mount lights will get a threaded plate that attaches to the
top of the fixture to allow for pipe to be threaded directly into it.
Using the provided gasket in the groove on the underside of the
plate, pull the wiring through the threaded hole on the plate and
secure it to the fixture using the provided hardware kit. There
should be one screw and one lock washer for each hole. Be sure
the gasket stays in position and provides a good seal once the
screws are secure. Fixture is now ready to be pendant mounted.
Follow all applicable local and national electrical and building
codes when completing the installation.
Ceiling:
Ceiling mount lights will get a surface mount junction box to mount
to the top of the fixture that will allow it to be mounted to any flat
surface capable of supporting the load. Using the provided gasket
to seal between the junction box and the fixture, attach the junction box to the fixture using the provided hardware kit, pulling
the wiring into the junction box to allow for connections. There should be one screw and one lock washer for each hole. Be
sure the gasket stays in position and provides a good seal once the screws are secure. Fixture is now ready to be surface
mounted using the pre-drilled mounting holes in the flange of the base.
Wall:
Wall mount lights will get a surface mount junction box and elbow extension to mount to the top of the fixture that will allow it
to be mounted to a wall. Using the provided gasket to seal between the junction box and elbow extension, attach the two
pieces together using the provided hardware, as shown in the picture above. Once the elbow extension and junction box
-Pendant