Func
Code
Name
Range
Min
Unit
Factory
Default
Modify
P2 Group: Start/Brake function parameter
P2
.
00
Start running
mode
0: Start from start freq.
1: Brake first, then start from start
freq.
2: Track speed, then start.
1
0
×
P2
.
01
Start freq.
0.40
~
20.00Hz
0.01Hz
0.50Hz
○
P2
.
02
Start freq.
running
duration
0.0
~
30.0s
0.1s
0.0s
○
P2
.
03
DC brake
current as
start
0
~
15%
1%
0%
○
P2
.
04
DC brake
time as start
0.0
~
60.0s
0.1s
0.0s
○
P2
.
05
Stop mode
0: Dec
1: Free Stop
2: Dec+ DC brake
1
0
×
P2
.
06
Start freq. of
DC brake as
stop
0.0
~
15.00Hz
0.0Hz
3.00Hz
○
P2
.
07
DC brake
time as stop
0.0
~
60.0s
0.1s
0.0s
○
P2
.
08
DC brake
current as
stop
0
~
15%
1%
0%
○
P3 Group :Auxiliary running parameter
P3
.
00
Freq. control
channel
combination
0: VI
+
CI
1: VI
-
CI
2: External pulse given
+
VI
+
control panel
▲
、
▼
key given
3: External pulse given
-
VI
-
control panel
▲
、
▼
key given
4: External pulse given
+
CI
5: External pulse given
-
CI
6: RS485 given
+
VI
+
control
panel
▲
、
▼
key given
7: RS485 given
-
VI
-
control
panel
▲
、
▼
key given
8: RS485 given
+
CI
+
control
panel
▲
、
▼
key given
1
0
×
Larson Electronics, LLC
Phone:
Fax: (903) 498-3364
www.larsonelectronics.com
20
of
52
VFD-1P-220.240-1HP-7A-DCM
(877) 348-9680