3

 

Return to Table of Contents

 

LED Indicator

 

Status

 

One Flash Red

 

Replace Electronics

 

Two Flashes Red

 

Replace Battery

 

Four Flashes Red

 

Replace Lamp Head

 

Board

 

Five Flashes Red

 

Replace Remote Lamp 
Head or Remote Lamp 
Head is Disconnected

 

Steady Red

 

Power Is Connected

 

Solid Green

 

Trickle Charge

 

Flashing Green

 

In Test

 

Red/Green Flashing

 

High Charge

 

 

 

 

 

 

 

 

II. Self-Diagnostic Test

 

 

Once the emergency fixture is properly installed and AC power supplied, the dual color LED 
indicator will come ON and the self-diagnostic test function will automatically initiate. The LED 
indicates the unit’s status. A STEADY GREEN LED indicates normal service, a FLASHING GREEN 
LED indicates the unit is testing, a FLASHING GREEN/RED LED indicates the battery is charging 
and a RED LED (in different combinations) indicates a service alert. Refer to the service indication 
chart for more details. The LED will be OFF when the unit is in emergency mode.

 

 

 

I. Self-Diagnostic Service

 

 

 

The self-diagnostic function is factory preset 
and performs the following:

 

 

1. Monitoring of battery, battery charger and 
lamps.

 

 

2. Self-testing and a 30-second or longer 
discharge once every 30 days, after AC 
power has been supplied for a minimum of 24 
hours.

 

 

3. Self-testing and a 30-minute or longer 
discharge once every 180 days, after AC 
power has been supplied for a minimum of 24 
hours.

 

 

4. Self-testing and a 90-minute discharge 
once every 365 days, after AC power has 
been supplied for a minimum of 24 hours.

 

II. Service Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание EXP-EMG-EXT series

Страница 1: ...EXP EMG EXT Explosion Proof Bug Eye Emergency LED Fixture Instruction Manual for the EXP EMG EXT Product Line Pictures not the same on every model...

Страница 2: ...nstructions will insure many years of safe and dependable service Table of Contents I Installation Operation 2 I I Installation 2 I II Operation 2 II Self Diagnostic Testing 3 II I Self Diagnostic Ser...

Страница 3: ...n the back side of the light The EXP EMG EXT explosion proof emergency self testing LED fixture is NOT a factory sealed fixture Operators will bring their own rigid conduit to a junction box and compl...

Страница 4: ...light The LED indicator should turn RED 2 In the event of power loss the fixture will illuminate all lights automatically Once power is restored the lights will turn off and the batteries will charge...

Страница 5: ...LASHING GREEN LED indicates the unit is testing a FLASHING GREEN RED LED indicates the battery is charging and a RED LED in different combinations indicates a service alert Refer to the service indica...

Страница 6: ...However it should be tested periodically and replaced when it no longer operates the connected fixtures for the duration of a 30 second or 90 minute test 2 Other Clean lenses and replace lamps as and...

Страница 7: ...d installation Disconnect AC power before servicing and installation DO NOT use this electrical equipment for anything other than its intended use The use of accessory equipment is not recommended by...