PLUG OPERATION 

Electrical  connection  between  plug  and  compatible  receptacle  is  accomplished 

after plug fully inserts into receptacle and rotated clockwise. 

1.

Lift  receptacle  door  and  locate  polarization  on  mating  plug  pin  and

receptacle  face.  Insert  plug  straight  all  the  way  into  receptacle  until  it

cannot go further.

2.

Rotate  plug  clockwise  limit  (37º),  this  closes  internal  contacts  and

completes  circuit.  This  also  mechanically  locks  plug  into  receptacle  so  it

cannot be pulled out.

3.

To remove plug, push plug inward and turn to counterclockwise, pull plug

straight out.

MOUNTING

The  explosion  proof  receptacle  features  four,  1/4"  mounting  holes  at  every  corner  of  the  unit  for  permanent  mounting 

installations.

INSTALLATION 

1.

Mount back box in desired position following methods that comply with NEC and

 

any local codes.

CAUTION:

 Conduit sealing fittings MUST BE installed in Class 1, Group B

 

locations to comply with the requirements 

in the latest edition of the NEC,

 

Section 501-5 and/or 502-5 plus any other applicable standards. Sealing fittings

 

must 

be close-nippled to the enclosure.

2.

Pull all power source wiring into back box. Be sure wires are long enough to

 

make proper connections.

CAUTION:

 Use only copper or copper-clad wire with this receptacle.

3.

Attach power source conductors to receptacle terminals in an approved manner.

 

Black conductor is attached to 

bronze screw; white conductor is attached to

 

silver cadmium screw; and green grounding conductor is attached to the 

green

 

screw.

4.

Push wiring into back box and attach receptacle using the four screws provided.

 

The preferred arrangement for the 

receptacle is with the door hinge on top.

 

Tighten screws to 30 inch-pounds torque.

OPERATION 

1.

Insert plug into receptacle as far as it will go.

2.

Turn clockwise as far as it can go. Internal contacts of the receptacle are closed

 by this action and complete the 

electrical circuit.

3.

Release plug allowing it to move outwardly slightly, into a locking detent position.

 

Check by trying to turn and/or pull 

out without any inward pressure. Plug should

 

not pull out.

4.

To remove plug, press inward, turn counterclockwise and pull straight out.

Figure 1 

 “QW” TERMINAL CONNECTIONS

QW  WIRING  (See Figure 1) :

NOTE

: Use 

only

 copper wire with this device (10, 12

 

or 14 AWG).  

Recommended wire strip length – ½

 

inch nominal (wire strip gauge also 

available on the

 

QW terminal cover).  Loosen all (3) Terminal Contact

 

Screws 

and insert wire through the Wiring Entrance

 

holes, into proper terminals: 

Green lead (Ground)

to terminal with ground mark & Green screw head;

 

White (Neutral) lead to 

terminal with Silver screw

 

head (125V. only); Black and/or Red [Line lead(s)]

to terminal(s) with Brass screw head.  Hand tighten

 

terminal screws 

(recommended torque 8 in.-lbs.

Содержание EPO-20A

Страница 1: ...STRUCTIONS FOR FUTURE REFERENCE THE EPO 20A MUST BE WIRED IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE AND ALL APPLICABLE LOCAL CODES PROPER GROUNDING IS REQUIRED FOR SAFETY WE STRONGLY ENCOURAGE ONLY A LICENSED ELECTRICIAN INSTALL OPERATE AND MAINTAIN THIS PRODUCT IF YOU ARE NOT QUALIFIED OR UNFAMILIAR WITH ANY ASPECT OF THIS INSTRUCTION SHEET CONSULT AN ELECTRICIAN THERE ARE NO SERVICEABLE PARTS ...

Страница 2: ...KS OR ANY SEVERE ABRASIONS AND IF ANY ARE FOUND THE CORD MUST BE REPLACED BEFORE RESUMING USE OF THE UNIT ELECTRICAL POWER SUPPLY MUST BE OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE INSTALLATION AND MAINTENANCE PROCEDURE MUST BE PERFORMED BY A TRAINED AND COMPETENT ELECTRICIAN IF ANY PARTS OF THE RECEPTACLE OR PLUG APPEAR TO BE MISSING BROKEN OR SHOW SIGNS OR DAMAGE DISCONTINUE USE IMMEDIAT...

Страница 3: ...pper or copper clad wire with this receptacle 3 Attach power source conductors to receptacle terminals in an approved manner Black conductor is attached to bronze screw white conductor is attached to silver cadmium screw and green grounding conductor is attached to the green screw 4 Push wiring into back box and attach receptacle using the four screws provided The preferred arrangement for the rec...

Страница 4: ... INSTALLATION REQUIREMENTS SHOULD FURTHER INFORMATION NOT COVERED BY THESE INSTRUCTIONS BE REQUIRED PLEASE CONTACT LARSON ELECTRONICS BY EMAIL AT SALES LARSONELECTRONICS COM OR BY PHONE AT 1 800 369 6671 FOR FURTHER ASSISTANCE PLEASE VISIT LARSONELECTRONICS COM FOR WARRANTY AND RETURN INFORMATION MAINTENANCE Perform visual electrical and mechanical checks of all components on a regular schedule Th...

Отзывы: