44428235
Assembly instruction
Valid from
28.07.2021
EPIC
®
SOLAR 4PLUS
Document: L44428235EN
Version: 03
Page 3 of 8
We reserve all rights according to DIN ISO 16016.
Safety Instructions
The EPIC
®
SOLAR 4PLUS connector is not suitable for mating and unmating under load.
De-energize the circuit by appropriate measures, e.g. at the inverter. Disconnecting and also
plugging in is possible without load, while voltage is present.
EPIC
®
SOLAR 4PLUS connectors are intended for connecting stationary photovoltaic systems.
They are suitable for fixed installation in dry and damp rooms, as well as outdoors. EPIC
®
SOLAR products are not suitable for underground installation.
PV-Cables:
Label:
LAPP KABEL H1Z2Z2-K
Cable code:
H1Z2Z2-K
Rated cross-section:
4,0 mm²; 6,0 mm², 10,0 mm²
Rated Voltage:
AC U0/U 1,0/1,0 kV; DC 1,5 kV
Max. Voltage
DC 1,8 kV (Conductor/Earth) System without Earth
connection
Mated connectors are IP68 protected (1m/10h). Continuous ooperation under water, e.g.
water on the roof skin of a flat roof is not possible.
EPIC
®
SOLAR connectors may only be assembled using tools and aids specified by Lapp. The
cable may only be connected to the connector by trained electricians. To protect the installer
from the danger of the electric current, the connector must be made floating on all sides during
installation.
Unplugged connectors must to be protected against ingress of dirt and moisture. Before
plugging together, make sure that the mating area is free of any dirt.
Note
:The PV Connectors EPIC SOLAR 4 Plus are not rewireable.
Defective connectors can be replaced by new connectors of the same type and
connection cross-section, complying with all requirements of this installation
instruction and having ensured that the cabel is without voltage and not under load.