lapara 10KR Скачать руководство пользователя страница 21

20 

 

20

LA-ON31-RACK 

z

 

02: Output frequency   

Interface Setting 

60 Hz, CVCF mode 

 

50 Hz, Normal mode 

 

ATO 

 

Parameter 2: Output Frequency 

Setting the output frequency. You may choose following three 
options in parameter 2: 

50.0Hz: 

The output frequency is setting for 50.0Hz.   

60.0Hz:

 The output frequency is setting for 60.0Hz. 

ATO:

 If selected, output frequency will be decided according to the 

latest normal utility frequency. If it is from 46Hz to 54Hz, the output 
frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the output 
frequency will be 60.0Hz. ATO is default setting. 
 

Parameter 3: Frequency mode 

Setting output frequency at CVCF mode or not CVCF mode. You 
may choose following two options in parameter 3: 

CF:

 Setting UPS to CVCF mode. If selected, the output frequency will 

be fixed at 50Hz or 60Hz according to setting in parameter 2. The 
input frequency could be from 46Hz to 64Hz. 

NCF:

 Setting UPS to normal mode (not CVCF mode). If selected, the 

output frequency will synchronize with the input frequency within 
46~54 Hz at 50Hz or within 56~64 Hz at 60Hz according to setting in 
parameter 2. If 50 Hz selected in parameter 2, UPS will transfer to 
battery mode when input frequency is not within 46~54 Hz. If 60Hz 
selected in parameter 2, UPS will transfer to battery mode when input 
frequency is not within 56~64 Hz.   
*If Parameter 2 is ATO, the Parameter 3 will show the current 
frequency. 

Note: For single unit, it will have bypass output for a couple of seconds after the unit is powered on. 

Therefore, to avoid damage on connected devices, it is strongly suggested to add an additional 
Output relay board for CVCF application. 

z

 

03: Voltage range for bypass   

Interface Setting 

 

Parameter 2: 

Set the acceptable low voltage for bypass. Setting 

range is from 110V to 209V and the default value is 110V. 

Parameter 3: 

Set the acceptable high voltage for bypass. Setting 

range is from 231V to 276V and the default value is 264V. 

04: Frequency range for bypass 

Interface Setting 

 

Parameter 2:

 Set the acceptable low frequency for bypass.   

50 Hz system: Setting range is from 46.0Hz to 49.0Hz. 
60 Hz system: Setting range is from 56.0Hz to 59.0Hz. 
The default value is 46.0Hz/56.0Hz. 

Parameter 3: 

Set the acceptable high frequency for bypass.   

50 Hz: Setting range is from 51.0Hz to 54.0 Hz.   
60 Hz: Setting range is from 61.0Hz to 64.0Hz. 
The default value is 54.0Hz/64.0Hz. 

z

 

05: ECO mode enable/disable 

Interface Setting 

 

Parameter 3: 

Enable or disable ECO function. You may choose 

following two options: 

DIS: 

disable ECO function   

ENA:

 enable ECO function   

If ECO function is disabled, voltage range and frequency range for 
ECO mode still can be set, but it is meaningless unless the ECO 
function is enabled. 

 

Содержание 10KR

Страница 1: ...EN USER MANUAL 3Ph 1Ph 10K 20K RACK Online UPS Uninterruptible Power Supply System...

Страница 2: ...operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all sa...

Страница 3: ...LLATION FOR PARALLEL SYSTEM 9 2 5 SOFTWARE INSTALLATION 11 3 OPERATIONS 12 3 1 BUTTON OPERATION ERROR MARCADOR NO DEFINIDO 3 2 LED INDICATORS AND LCD PANEL 12 3 3 AUDIBLE ALARM 14 3 4 SINGLE UPS OPERA...

Страница 4: ...onnect appliances or devices that would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not...

Страница 5: ...hat no liquid or other foreign objects can enter into the UPS system otherwise guarantee would not be accepted The UPS can be operated by any individuals with no previous experience 1 5 Standards Safe...

Страница 6: ...Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option One USB cable One parallel cable only availab...

Страница 7: ...6 6 LA ON31 RACK Diagram 2 15KR L 20KR L Rear Panel Diagram 3 10KR 10KR L Input Output Terminal Diagram 4 15KR L 20KR L Input Output Terminal...

Страница 8: ...ctions must be executed by professional personnel 1 Make sure that the mains wire and breake avoid the hazards of electric shock or fire NOTE Do not use the wall receptacle as the input power source f...

Страница 9: ...leakage current protective function if necessary 6 Put the terminal block cover back to the rear panel of the UPS Warning Only for standard model Make sure that the UPS is not turned on before instal...

Страница 10: ...onnection and conductance reliability should be checked carefully Make sure the utility input output wiring is correct The wire current spec color position connection and conductance reliability shoul...

Страница 11: ...m for 15KR L 20KR L 2 5 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown Install CD or visit the website http www laparaups...

Страница 12: ...button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press th...

Страница 13: ...cy Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the output is short Mode operation information Indicates the UPS connects to the ma...

Страница 14: ...Over temperature Overload UPS Model abnormal Continuously beeping Yes 3 4 Single UPS Operation 1 Turn on the UPS with utility power supply in AC mode 1 After power supply is connected correctly set th...

Страница 15: ...disabled or the input power is not within bypass acceptable range it will cut off output directly 4 Charge the batteries 1 After the UPS is connected to the utility power the charger will charge the...

Страница 16: ...se refer to section 3 3 for the details 10 Operation in warning status 1 When Fault LED flashes and the buzzer beeps once every second it means that there are some problems for UPS operation Users can...

Страница 17: ...utility power supply in AC mode a Turn on the input breaker of each UPS After all UPSs enter to bypass mode measure the voltage difference between the output of each UPS with a multimeter If the volt...

Страница 18: ...h UPS and then turn off the running system All UPSs will transfer to bypass mode Remove all the maintenance bypass covers and set the maintenance switches from UPS to BPS Turn off all the input breake...

Страница 19: ...the UPS Refer to following diagram Parameter 1 It is for program alternatives There are 14 programs to set up Refer to below table Parameter 2 and parameter 3 are the setting options or values for eac...

Страница 20: ...Y Y Yes means that this program can be set in this mode It is only available to operate when a loss of neutral line is detected Otherwise it will display in program setting menu This function can get...

Страница 21: ...will transfer to battery mode when input frequency is not within 56 64 Hz If Parameter 2 is ATO the Parameter 3 will show the current frequency Note For single unit it will have bypass output for a c...

Страница 22: ...g Parameter 2 OPN Bypass allowed When selected UPS will run at Bypass mode depending on bypass enabled disabled setting FBD Bypass not allowed When selected it s not allowed for running in Bypass mode...

Страница 23: ...3 when entering the setting menu next time z 13 Battery voltage adjustment Interface Setting Parameter 2 Select Add or Sub function to adjust battery voltage to real figure Parameter 3 the voltage ran...

Страница 24: ...which L2 delay L1 120 L3 delay L2 120 or L2 delay L1 240 L3 delay L2 240 3 8 Operating Mode Status Description The following table shows LCD display for operating modes and status 1 If the UPS is in...

Страница 25: ...r into no output mode if powering on or turning off the UPS It means that the UPS has no output Alarm beeps every two minutes No output mode LCD Display Description When the input voltage is within ac...

Страница 26: ...g ECO mode LCD display Description When input frequency is within 46 64Hz the UPS can be set at a constant output frequency 50Hz or 60Hz The UPS will still charge battery in this mode CVCF mode LCD di...

Страница 27: ...ss mode LCD display Description When UPS is in AC mode or CVCF mode press Test key for more than 0 5s Then the UPS will beep once and start Battery Test The line between I P and inverter icons will bl...

Страница 28: ...cond Battery unconnected Beeping every second Over charge Beeping every second EPO enable Beeping every second Fan failure Over temperature Beeping every second Charger failure Beeping every second I...

Страница 29: ...excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becomes faul...

Страница 30: ...with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery termin...

Страница 31: ...urrent 1 A 10 max 2 A 10 max Standard Model Charging Voltage 14 4 V 1 Type Depending on applications Numbers 18 20 Charging Current 4 A 10 max Long run Model Charging Voltage 14 4 V 1 PHYSICAL Dimensi...

Отзывы: