LA-ON31-RACK
Programs available list for parameter 1:
Code Description
Bypass/
No-output mode
AC
Mode
ECO
Mode
CVCF
Mode
Battery
Mode
Battery
Test
01
Output voltage
Y*
02
Output frequency
Y
03
Voltage range for bypass
Y
04
Frequency range for bypass
Y
05
ECO mode enable/disable
Y
06
Voltage range for ECO mode
Y
07
ECO mode frequency range setting
Y
08
Bypass mode setting
Y Y
09
Battery backup time setting
Y Y
Y
Y
Y
Y
10
Programmable output setting
11
Shutdown point f/programmable output
These functions are not supported by the Rack model
12
Reserved/Neutral Loss **
13
Battery voltage adjustment
Y
Y
Y
Y
Y
Y
14
Charger voltage adjustment
Y
Y
Y
Y
Y
Y
15
Inverter voltage adjustment
Y
Y
Y
16
Output voltage calibration
Y
Y
Y
17
Phase auto adapt enable/disable***
Y
*Y (Yes) means that this program can be set in this mode.
**It is only available to operate when a loss of neutral line is detected. Otherwise, it will display “
” in program
setting menu.
***This function can get UPS input phase sequence more flexible. If it is enabled, UPS can adapt several kind of
phase order even it works like single phase UPS. If it is disabled, UPS can only work under standard input phase
sequence between L1/L2/L3. For more details about LCD setting, please refer to program 17 below.
Note: All parameter settings will be saved only when UPS shuts down normally with internal or external battery
connection. (Normal UPS shutdown means turning off input breaker in bypass/no output mode)
z
01: Output voltage
Interface Setting
Parameter 3: Output voltage
You may choose the following output voltage in parameter 3:
208:
Presents output voltage is 208Vac
220:
Presents output voltage is 220Vac
230:
Presents output voltage is 230Vac
240:
Presents output voltage is 240Vac