background image

 

 

3

 

Product description 

3.1

 

Dimensions 

 

 

 

Fig. 1 

 

Fig. 2 

3.2

 

Technical data 

Housing material 

Stainless steel 

Protection class 

Degree of protection 

IP47 

Power consumption 

Typically 36 W | maximum 54 W 

Ambient temperature 

-25°C to +38°C 

Weight 

Approx. 8 kg 

Connection cable 

3x 1.5 mm² 

Adjustable / switching point 

-15 ° - +45 ° 

510 mm

 

4

80

 mm

 

1

5

0

 mm

 

Содержание EK890

Страница 1: ...Operating Instructions Air circulation EK890...

Страница 2: ...ion 4 3 1 Dimensions 4 3 2 Technical data 4 3 3 Operating voltages 5 4 Required tools 5 5 Changing the fan unit 6 6 Commissioning 6 7 Function test 8 8 Fan supply outlets 9 9 Maintenance 10 10 EU Decl...

Страница 3: ...afety information The product corresponds to the latest state of the art technology at the time of printing and is delivered in an operationally safe condition Unauthorised modifications particularly...

Страница 4: ...l data Housing material Stainless steel Protection class I Degree of protection IP47 Power consumption Typically 36 W maximum 54 W Ambient temperature 25 C to 38 C Weight Approx 8 kg Connection cable...

Страница 5: ...t Power 60 watts 24 VDC Per fan 24 VDC 12 watts Air flow per fan 285 m h Noise level 55 dB per fan Fan speed 5000 rpm 3 3 Operating voltages Designation Core Minimum Maximum Unit Permanent operating v...

Страница 6: ...ng the fan unit Loosen 4 x cross head screws 1 Note disconnect the unit from the mains voltage before removing it Fig 4 6 Commissioning Fig 5 Power the cold device plug input with 230 VAC operating vo...

Страница 7: ...the residual current device 1 Fig 7 Green LED from the control element and blue LED from the power supply unit light up red LED does not Fig 8 Place the temperature sensor 1 in the device at the hott...

Страница 8: ...start Red LED lights up Lower temperature at the installation site than setting on the control element Fans stop Red LED goes out e g outdoor temperature 20 setting on the control element 15 Fans run...

Страница 9: ...9 8 Fan supply outlets Fig 11 Service socket 1 outlet side fused via RCD circuit breaker Fig 12 Cold device socket 1 outlet side fused via RCD circuit breaker 1 1...

Страница 10: ...laration of Conformity for this product can be requested from Langmatz GmbH Measures Intervals Remarks External visual inspection At least every 12 months or during maintenance measures on the complet...

Страница 11: ...r hotline see Chapter 13 Disclaimer Warranty The information in this technical document is presented appropriately and correctly in accordance with the technical regulations and to the best of our kno...

Страница 12: ...12 79 100 0074 001 As of 22 03 2022 Translation of the Original Installation Instructions...

Отзывы: