SPECIFICATIONS
Operation & Maintenance Manual
02
2.1 - Standards and Operating Conditions:
Applicable standard: IEC 129.
Operating conditions: Switch is mounted in type GV cubicle with minimum gas pressure of 1.2 bars absolute above atmosphere at
20°C.
2.2 - Technical Data:
Electrical Characteristics
Rated Voltage
2500A
Table 2.2 - Technical Data
2.0 SPECIFICATIONS
2000A
1250A
630A
kV
Rated Current
Rated Frequency
Rated Short Time Current
Rated short circuit
Making Current
Rated short circuit symmetric
breaking Current
Rated Lighting Impulse
Voltage (1.2/50 Micro Sec.)
Rated a.c. 1 min pf voltage
A
Hz
kA/3sec
kAp
kA
kVp
kV rms
36
50
630
1250
2000
2500
26.3/31.5
63/80
26.3/31.5
170
70
SF6 Gas Sealing Pressure
kg/cm²
0
abS@20 C
1.35
Operating method
Motor-spring/ Manual-spring operation
Operation Voltage
48 / 110 / 220 V DC
Operation Current
1-3.5A at 48 / 110 / 220 V DC
Mechanical operation life
2000 operations