29
Extender Configuration in
Command Center
Overview
Similar to endpoints, Extenders will auto-register to Command Center. After the Extender has been
installed, it will attempt to auto register. For the Extender auto registration to complete successfully,
the following prerequisites must be observed.
•
Correct Network ID must be coded into the Extender
•
The Extender must be in Operational Mode
•
The Extender must be loaded with Firmware version 4.0a .11 or later
•
No WAN Address loaded into the Extender
•
No GEO coordinates (LAT/LONG), loaded into the Extender
To complete the auto-registration process, a Meter Manufacturer File (MMF) must be imported into
Command Center.
Importing Extenders into Command Center
Meter Manufacturer File
The Meter Manufacturer File provides Command Center with information on the Extender ID and
the module serial number. This file is not currently provided at the time the Extenders are purchased,
and must be created using the MMF.csv template.
Create a Meter Manufacturer Data File
1.
Click
Operations > Import > Meter Manufacturer Data
to display the Import Meter
Manufacturer Data screen shown in Figure 4 - 1.
Figure 4 - 1. Import Meter Manufacturer Data
DRAFT
5.14.2012