![Landis+Gyr E230 Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/landis-gyr/e230/e230_user-manual_673713050.webp)
50/84
Operation
© Gyr
D000044352 en g – E230 Residential Electricity Meter – ZxR100xC/ZMR100xR – User Manual
Event
no.
Name
Description
Trigger
Event Anti-
fraud
Perma-
nent
trigger
(confi-
gurable)
8 Billing
period
reset
Indicates that a billing period
reset has occurred.
X
9 Daylight
saving time
enabled or
disabled
Indicates a change from and to
daylight saving time. The time
stamp shows the time before
the change.
X
10 Clock
adjusted (old
date/time)
Indicates that the date/time
has been adjusted. The time
that is stored in the event log is
the old time before the
adjustment was made.
X
11 Clock
adjusted
(new
date/time)
Indicates that the date/time
has been adjusted. The time
that is stored in the event log is
the new time after the
adjustment was made.
X
17, 18,
19
Under-
voltage L1,
L2, L3
Indicates that an undervoltage
has occurred on the
corresponding phase.
X
20, 21,
22
Overvoltage
L1, L2, L3
Indicates that an overvoltage
has occurred on the
corresponding phase.
X
23
Power down
Indicates that a power failure
has occurred.
X
24
Power up
Indicates that a power up has
occurred.
X
25, 26,
27
Overcurrent
L1, L2, L3
Indicates that an overcurrent
has occurred on the
corresponding phase.
X
28, 29,
30
Voltage
without
current L1,
L2, L3
Indicates a possible shorting of
the current coil.
X X
31 Power
factor
monitor 1
Indicates that the power factor
is below a set limit.
X
33, 34,
35, 36
Demand
monitors 1, 2,
3 and 4
Indicates that the demand is
above a set limit.
X
37, 38,
39
Phase
reversal L1,
L2, L3
Indicates a reversal of polarity
of the current coil.
X X