12
3
For Your Safety
3.6.3
Checking Burner Sequencer Part
Check the following:
•
Correct setting of time parameters (especially safety and pre-purge periods).
•
Whether an ionisation or approved self-checking flame sensor is used as only these types
allow continuous operation.
•
Functioning of flame sensor
–
in case of flame blow-off during operation
–
parasitic light being present during pre-purge period
–
missing flame formation at the end of the safety-period
•
Check the performance of all available and/or essential incoming signals, such as:
–
Air pressure switch
–
Gas pressure - min./oil pressure - min.
–
Safety interlock chain (e.g. STB)
•
Activated leakage control function for gas valves if required for application purposes.
–
If necessary, ensure a correct leakage quantification.