CURRENT CONTROL RELAYS ADJUSTING AND
CONNECTING
These values are default values you can get change those
values.
Relays have to adjust always case sensitive.
1.
Choice correct current area
•
Turn switch 2 position ON (when main
fuse are less than 50A)
•
Others switchs 1,3-6 position OFF.
2.
Adjust hyseresis current % and delay
srews from the front (main fuse 25A)
•
Hysteresis
21
•
Current
25 - 28 %
•
Delay
1s
• Relay need external power 24-240 V/AC.
• External power connect connectors A1 and A2.
• Connectors 15 and 16 connect ground heat pump and those
cut power on the immersion heaters those line what current
limit are exceed.
• Every line must be lead through to relays.
• L1 1- relay
• L2 2- relay
• L3 3- relay
HYSTERESE
SWITCHES ARE UNDER THE COVER
CURRENT
DELAY