Lambrecht EOLOS-IND Скачать руководство пользователя страница 10

Manual
Weather Sensor EOLOS-IND Modbus 

(1643) EOLOS-IND Modbus 

  

 

      Manual 

Holding Register

Register address 40001 to 49000

Register addresses 40001 to 46000 contain the confi guration parameters of the sensor. 

Register address 46001-49000 Contain the available registers for each sensor with measured values and sensor data from 
the range 30001-35000.

7.1 

Sensor Parameters / Confi guration Parameters

Register 
address

Parameter name 

Unit

Divisor

Description

40001 Modbus device address

1

The addresses 1...247 are allowed.

40200 Baud rate

0,01

96=9600
192=19200
384=38400

46000 Number of mapping registers

Contains the number of occupied map-
ping registers for autoconfi guration, with 
EOLOS-IND = 40

INT

7.2 

Register Mask for Autoconfi guration - Mapping Register

Register address 46001-49000. Contains the available registers for each sensor with measured values and sensor data from 
the range 30001-35000.

The registers can only be read out as a block! The length of the block or the number of available mapping registers can be 
found in holding register 46000.

E.g. at the Modbus-Pro-WG there are valid addresses in registers 46001 to 46004. Holding register 46000 contains the number 
of registers 4. All 4 registers must be read out in the block with command 0x04. Too many registers or too few lead to an error 
message.

Autoconfi guration

The Modbus sensors from LAMBRECHT meteo off er the possibility of autoconfi guration. This is supported e.g. by the data 
logger met[LOG]. For autoconfi guration, the register addresses of the measured values and sensor data available in the register 
range 30001 to 35000 are listed as consecutive values in the register range 46001 to 49000 in the LAMBRECHT sensors. 
Registers 46001 to 49000 can only be read out as blocks! The length of the block or the number of available mapping registers 
can be found in holding register 46000. 

Since the addresses from the range 30001 to 35000 are valid for all LAMBRECHT sensors, an address from this range is also 
representative of a measured value type.
E.g. register 30401 always contains the instantaneous value of the air temperature. If this register address is not contained in 
the list in register range 46001 to 49000, the connected Modbus sensor does not supply an air temperature. 

If the autoconfi guration is started with the data logger met[LOG], it queries the existing mapping registers on each COM 
interface in the device address range 1...25. For this purpose, the number of mapping registers is read from register 46000 
and the register range from 46001 is read as a block.
The following table contains the assignment of the confi guration to the individual (possible) instantaneous value registers of 
the sensors. Some sensors supply registers with mean, minimum and maximum values or additional values in addition to this 
specifi cation. Unknown register addresses (or registers that are not required) must therefore be ignored during autoconfi guration.

10

Содержание EOLOS-IND

Страница 1: ...egrated overvoltage protection Simple space saving assembly on 50 mm standard pipe The Perfect Weather Sensor For industrial use as well as under extreme environmen tal conditions 5 1 1 parameters in...

Страница 2: ...Mounting 2 7 1 North Alignment of Wind Sensor 2 7 2 Power and Signal Connection 2 7 3 Safety Regulations 3 Maintenance 3 1 Regular Maintenance and Calibration 3 2 Visual Check and Cleaning 4 Transport...

Страница 3: ...is method Lightweight mass and immovable measuring elements to enable very low starting values distance and attenuation constants as well as a very high repetition accuracy The sensor can be installed...

Страница 4: ...t the mast if available If needed you can turn in or unscrew the pin by means of allen key 2 7 1 North Alignment of Wind Sensor For wind direction measurements the north mark on the sen sor must be al...

Страница 5: ...signal of the sensor corresponds to the RS 485 standard The signal levels allow transmission via shielded signal cables up to a maximum length of 1 200 meters or 4 000 feet The cable lengths depend o...

Страница 6: ...ngsscraube M8 fastening screw Erdscraube M6 earthing screw 10 1 5 6 0 1 P40 min P50 P48 3 5 6 0 1 10 1 min 40 P40 min 50 9 P 0 1 Aufnahmerohr f r den Sensor sensor seat pipe N Schlitz im Mastende baus...

Страница 7: ...ensor EOLOS IND Modbus 1643 EOLOS IND Modbus Manual 7 IN 24 V DC f r Elektronik for electronic Schirm shield Erde earth 287 56 0RGEXV 578 1 2 3 4 1 2 3 4 br wt bl bk PIN color 5 5 N A br ws bl sw Farb...

Страница 8: ...is transmitted in the order 0x12 0x34 Example big endian 32 bit or 64 bit Register size value 32 bits 0x12345678 is transmitted in the order 0x12 0x34 0x56 0x78 6 2 Device Address The addresses 1 247...

Страница 9: ...stantaneous value r h 10 1 decimal place INT 30602 Humidity mean value since last retrieval r h 10 1 decimal place INT 30603 Humidity maximum value r h 10 1 decimal place INT 30604 Humidity minimum va...

Страница 10: ...HT meteo o er the possibility of autocon guration This is supported e g by the data logger met LOG For autocon guration the register addresses of the measured values and sensor data available in the r...

Страница 11: ...imal places LONG 0x04 Big Endian WORD 31102 Precipitation amount total Low WORD 3 decimal places Registers 31101 31102 can only be read out together function code 0x04 0x04 Big Endian WORD 31201 Preci...

Страница 12: ...s 1 Dew point maximum value INT 46020 30703 Register address 1 Dew point minimum value INT 46021 30801 Register address 1 Air pressure instantaneous value INT 46022 30802 Register address 1 Air pressu...

Страница 13: ...100 r h Parameters Wind direction Measuring range 0 360 Accuracy 3 RMS Resolution 1 Wind speed Measuring range 0 1 50 m s Accuracy 0 5 m s 5 RMS of the meas value at 5 1 40 m s Resolution 0 1 m s Air...

Отзывы: