(15190) PreLOG   

          Operating Instructions 

Operating Instructions
Data Logger PreLOG (15190)

Description of the Functions

Integrated Debouncing of the Reed Contact Pulse Signal

The PreLOG has an integrated debouncing attuned to the LAMBRECHT precipitation sensors (15189, 15188, 
1518H3).
Therefore a maximum of 4 pulses per second is allowed at a resolution factor (precipitation amount corresponding 
to an incoming pulse) 

 0.1. Then the min. distance between falling edges is 250 ms.

At a resolution factor < 0.1 the debouncing will be changed automatically and the min. closing time will be 10 ms 
and the max. pulse frequency 50 Hz.

Linearisation of the Precipitation Signal - Precipitation Correction of the Recorded Pulses

Precipitation sensors using tipping buckets generally have an intensity-dependent error. The PreLOG has integrated 
precipitation correction compatible with the LAMBRECHT precipitation sensors 15189, 15188 and 1518H3. With 
activated correction the PreLOG records the corrected factor with the timestamp instead of the originally set 
resolution factor (see “

Recording of Precipitation Pulses With Timestamp

”).

Without correction the pulses are recorded with the originally set factor and a timestamp.

Using the intensity correction in combination with precipitation sensors of other manufacturers may result in incor-
rect measured values. Therefore the intensity correction should be deactivated in such cases.

Since some LAMBRECHT precipitation sensors already have integrated intensity correction, the correction of the 
PreLOG has to be deactivated if used with these sensors. Otherwise “double” correction would lead to incorrect 
results.

Confi guration

The precipitation correction can be activated or deactivated in the PreLOG-Commander in the area “

Setup – 

PreLOG Con

fi

 guration – General – Operating Mode

” as “

Signal Linearisation

.”

Tip: The integrated precipitation correction can only be activated at resolution factors 

 0.1. 

At smaller resolution factors (< 0.1) the PreLOG automatically deactivates the correction.

Pulse Output

If another device should process the precipitation pulses, the received pulse can be output by the PreLOG by 
activating its pulse output. The length of the output pulse depends on the speci

fi

 ed resolution factor. At resolution 

factors 

 0.1 the closing time (pulse length) is 125 ms. At resolution factors < 0.1 the closing time is reduced to 

10 ms.

Attention! Please note that the pulse output of the PreLOG is not galvanically isolated!

Confi guration

The pulse output can be activated or deactivated in the PreLOG-Commander in the area “

Setup – PreLOG 

Con

fi

 guration – General – Operating Mode

” at “

Pulse Output Active

.”

10ms Schließzeit / closing time

max. 50 Hz

min. 250 ms

Schließzeit / closing time

Fig. 12

Permitted pulses with resolution factor < 0.1

Permitted pulses with resolution factor 

 0.1

Содержание 15190

Страница 1: ...n intensity and without a modem Recharging of the battery via USB port Housing IP65 plugged in connector IP67 PreLOG Pulse output not corrected debounced Optional external power supply e g via solar s...

Страница 2: ...ander p 19 9 1 Initial Configuration of a PreLOG Quickstart S 19 9 2 Setup p 19 9 2 1 Setup Select Current Station p 19 9 2 2 Setup PreLOG Configuration p 20 9 2 3 Setup Set PreLOG Clock p 24 9 2 4 Se...

Страница 3: ...ines and or rules for the prevention of accidents e g 2 the professional association If necessary ask your responsible safety representative Use the system according to the manual s regulations only 3...

Страница 4: ...OG ECO PreLOG 5 Mounting You can mount the PreLOG directly to the LAMBRECHT precipitation sensor 15189 Therefore the precipitation sensor is already delivered with the necessary bore or an appropriate...

Страница 5: ...OG Operating Instructions Operating Instructions Data Logger PreLOG 15190 Another option is to mount the data logger to a mast with our special mast fixation from our traverse system Id No 32 14627 00...

Страница 6: ...tor see Fig 04 1 Trim the supplied cable to the desired length and remove the sheath on 2 cm 2 Use a straight cut to remove the shielding braid up to the edge of the sheath 3 Cut the not used strands...

Страница 7: ...t M12 Connector 8 Pin only PreLOG If the PreLOG should be read out via the RS232 interface externally powered or connected to the GPRS solar set the following pin assignment of the 8 pin M12 connector...

Страница 8: ...Modem via RS232 GSM If the PreLOG should always be accessible the control pin RS232 Communication ON 4 has to be connected to the Masse GND pin This operating mode needs the most energy since both th...

Страница 9: ...t retrieval or message Event message at exceeding of a max precipitation amount as moving sum of a specified period with hysteresis Event message at exceeding of a max precipitation intensity with hys...

Страница 10: ...ers may result in incor rect measured values Therefore the intensity correction should be deactivated in such cases Since some LAMBRECHT precipitation sensors already have integrated intensity correct...

Страница 11: ...me clock of the PreLOG is set by the function Setup Set PreLOG Clock of the PreLOG Commander By default the function suggests the date and time of the PC clock The circular buffer of the PreLOG can st...

Страница 12: ...eLOG Commander function Retrieval PreLOG Status After this retrieval the value will be reset to zero too Example Precipitation in mm m 21 318 Configuration The recording of the precipitation amount be...

Страница 13: ...e alarm Start of Precipitation can be activated in the PreLOG Commander in the tab Setup PreLOG Configuration Alarm Part 1 Furthermore the Amount Threshold in mm m as well as the Trigger Period period...

Страница 14: ...will be released if the intensity falls below a specified release intensity Configuration The alarm Exceeding of a Max Precipitation Intensity can be activated in the PreLOG Commander in the tab Setu...

Страница 15: ...ervice A well known example among others is DynDNS Such a dynamic DNS service automatically maps between the volatile IP address of the router that will change on every dial up but at the latest once...

Страница 16: ...1 RS232 for GSM communication see pp 20 ff Connect the PreLOG to a PC or notebook via USB or serial connection RS232 Select the PreLOG and the modem option Standard PC under Setup Select Current Stat...

Страница 17: ...Communication For the appropriate values see the corresponding sections in ch 9 2 2 on pp 20 ff and the documen tation of the modem in use if necessary Save and transmit the new configuration to the s...

Страница 18: ...nto the MeteoWare data base With the function 4 Utilities export the data can be exported in the formats MW MeteoWare Rain specific ASCII dBASE and Excel To receive data from a station the PC has to b...

Страница 19: ...of the ISO 8850 15 standard are allowed a Specify the COM port the PreLOG is connected to b Save the configuration by pressing the c Save button Retrieve the configuration of the connected PreLOG wit...

Страница 20: ...n number enter the station number 0 instead Request CFG you receive the configuration data of the connected station and thereby the current station number Before closing the window save the data by pr...

Страница 21: ...the connection if the communication starts right after the connection has been established The maximum number of dialing attempts can be specified in the field Max Redials If this limit is exceeded t...

Страница 22: ...e some modem types will cancel the connection if the communication starts right after connection has been established The following access data are necessary for a GPRS connection APN Accesspoint addr...

Страница 23: ...GPRS Test you can test if a GPRS connection can be established to the selected PreLOG In the process the command sequence to establish a connection via the selected GPRS modem will be executed by the...

Страница 24: ...control sequence which suits the telephone system the modem is connected to It has to be distinguished between tone and pulse dial as well as between main station or telephone exten sion for further...

Страница 25: ...ieval reset to zero afterwards Amount of Precipitation Since Switch On of the PreLOG Battery Status Percentage of Free Memory Most Recent GPRS Error Position of the Error in the Command Sequence The G...

Страница 26: ...cription of these critical errors can be displayed with the function PreLOG Critical Error If a critical error occurs please check the PreLOG immediately and contact the LAMBRECHT service department 4...

Страница 27: ...e LAMBRECHT service department and keep the entry from the GPRS LOG file within reach 10 3 Retrieval of PreLOG Configuration Failed Check in the tab Setup PreLOG Configuration General if the correct s...

Страница 28: ...l 49 0 551 4958 0 or 49 0 551 4958 390 E mail support lambrecht net 12 Equipment and Spare Parts General Accessories 00 90519 000 000 GPRS solar set 36 09338 010 000 Software MeteoWare Rain basic 36 0...

Страница 29: ...29 15190 PreLOG Operating Instructions Operating Instructions Data Logger PreLOG 15190 13 Space for Notes...

Страница 30: ...on via USB with PreLOG Commander Real time Clock typ 3 ppm at 15 C 60 C max 5 ppm at 25 C 65 C max 10ppm Rechargeable Battery 3 6 Li Ion exchangeable Ext Power Supply 12 V DC 9 26 V DC Caution Power s...

Отзывы: