RAGGIO C
191
EN
cod. 3541V280 - Rev. 01 - 04/2021
B06
Variable input contact
operation selection
Flow meter exclusion
System thermostat
Second room therm.
Warning/Alert
Safety thermostat
Second room thermostat
B07
Relay card LC32 selec-
tion
External gas valve
Alarm
System filling solenoid valve
Solar 3-way valve
Second heating pump
Alarm2,
Burner lit
Frost protection active
System filling solenoid valve
B08
Hours without DHW
draw-off
0 ÷ 24 hours (time for temporary deactivation of comfort
mode without draw-off)
24
B09
Fault 20 status selection
Deactivated
Enabled
Enabled
B10
Not implemented
--
--
B11
Flowmeter timing
Deactivated
1s ÷ 10s
(seconds)
Deactivated
B12
Modulation Delta
0 ÷ 30°C/10
0°C/10
B13
Not implemented
--
--
B14
Pump antiblock opera-
tion time
0 ÷ 20 seconds
5
B15
Flowmeter type selection
(b01=3)
Flow. (450 imp/l)
Flow. (700 imp/l)
Flow (190 imp/l)
Flow (190 imp/l)
B16
Fan frequency in standby
mode
0 ÷ 100%
0%
B17
NOT IMPLEMENTED
--
B18
DHW mode activation
flow rate
0 ÷ 100L/min/10
25
B19
DHW mode deactivation
flow rate
0 ÷ 100L/min/10
20
B20
Flue material selection
0
= Standard
1
= PVC
2
= CPVC
0
B21
PVC flue maximum tem-
perature
60 ÷ 110°C
88°C
B22
CPVC flue maximum
temperature
60 ÷ 110°C
93°C
B23
Standard flue shutdown
maximum temperature
60 ÷ 110°C
100°C
B24
PVC flue shutdown maxi-
mum temperature
60 ÷ 110°C
93°C
B25
CPVC flue shutdown
maximum temperature
60 ÷ 110°C
98°C
B26
Flow temperature limit in
automatic calibration
25°C ÷ 55°C
30°C
B27
Maximum temperature
during calibration in DHW
mode
75°C ÷ 95°C
80°C
Code Description
Range
Default