44
GB
OPERATING CYCLE
M
T11 = Air damper opening time, from 0 to max.
TW = Starts at the closing of the thermostat line and
the PG. The PA must be in the rest position. It is a
wait and self-test time.
T10 = Starts with the ignition of the motor and with
the pre-ventilation phase: it lasts 3 seconds, within
which the air pressure PA must give consent.
T1 = It is the pre-ventilation time that lasts a minimum
of 30 seconds and ends with the entry into operation
of the transformer.
T3 = It is the time that represents the pre-ignition
phase: it ends with the opening of the gas valve. It
lasts 3 seconds.
T2 = It is the safety time, within which the flame signal
must reach the EC electrode. It lasts 3 seconds.
T4 = This is an interval between the opening of the
V1 gas valve and the opening of the second stage
valve V2. It lasts 8 seconds.
T6 = Air damper closing and reset of the program
time.
T12 = Time in which the air damper moves to the
ignition position
Necessary input signals
Output signals
A = Start of ignition
B = Presence of flame
B-C = Operation
C = Stop Adjustment
TMF = Thermostat high/low flame
C-D = Damper c post ventilation
TC-PG = Thermostat lines/ gas pressure switch
MB = Burner motor
PA = Air pressure switch
TR= Ignition transformer
V1-V2 Gas valve 1-2 stage
EC = Control electrode
MT = Air actuator