IDOLA S 3.2

Error code

Unit 

in error

Malfunction or protection

Cause of fault and corrective action

Hd

IU

Communications error between the hydronic 

boards (for cascaded applications)

1.The signal cables of the slave and master units are not correctly connected. After checking that all 

the signal cables are securely connected and ensuring that there are no strong magnetic interfer-

ences, switch on again;

2. There are two or more hydronic boards connected to the user interface. Keep only one user inter-

face connected to the master unit and then, switch on again;

3. The start delay between the master and slave units is greater than 2 minutes. After ensuring that 

the interval between the start-up of the master unit and slave unit is less than 2 minutes, switch on 

again;

4. Conflict between the master and slave unit addresses:

When you press the SW2 button on the main slave unit board, the address code of the slave unit is 

displayed (the code used normally goes from 1, 2, 3 ... to 15); check if a there is a duplicated address. 

If there is a duplicated address, after switching off the system, set S4-1 to “ON” on the control unit 

hydronic board and on the hydronic board which displays the “Hd” error. Switch on all the units again, 

wait 5 minutes without the “Hd” error, switch off again and set S4-1 to “OFF”. The system will be reset. 

HE

IU

Communications error between the main board 

and the thermostat expansion board

The RT/Ta board is correctly configured on the user interface, but the thermostat expansion board 

is not connected or the communication between the board and the hydronic board is interrupted. 

HF

EU

Eprom EE error on the inverter module board 1. EEprom error; rewrite the data on the EEprom.

2. The EEprom is faulty; replace it with a new one.

3. The inverter module board is broken; replace it with a new one. 

HH

EU

H6 displayed 10 times in 2 hours

refer to H6

HP

EU

Low pressure protection in cooling Pe<0.6 oc-

curred 3 times in one hour

Refer to P0

L0

EU

Inverter module protection

-

L1

EU

Protection for low voltage on DC bus

-

L2

EU

Protection for high voltage on DC bus

-

L4

EU

MCE error

-

L5

EU

Zero speed protection

-

L7

EU

Phase sequence error

-

L8

EU

Frequency variation of the compressor greater 

than 15Hz per second 

-

L9

EU

Working frequency of the compressor different 

over 15Hz compared to target frequency.

-

P0

EU

Low pressure switch protection

1. The system has no refrigerant. Look for the leak, repair it and fill with the correct load.

2. The water flow is too low in cooling mode. Increase the water flow.

4. The electric expansion valve is blocked or the power supply has come loose. Try to release the 

valve by gently tapping it. Connect/disconnect the connector multiple times to ensure that the valve 

is working correctly. 

P1

EU

High pressure switch intervention

-

P3

EU

Compressor electrical current absorption great-

er than maximum limit allowed

-

P4

EU

Compressor drain temperature (Tp) greater 

than the maximum limit allowed

-

P5

IU

Temperature difference between Tw_out and 

Tw_in too high

1. Make sure that all the shut-off valves in the water circuit are completely open.

2. Check if the water filter need cleaning.

3. Make sure there is no air in the system (bleed the air).

4. Check the water pressure. The water pressure must be > 1 bar

5. Check that the pump speed setting is on the maximum speed.

6.Make sure that the expansion vessel is not broken.

7. Check that the resistance in the water circuit is not too high for the pump. 

P6

EU

Inverter module protection

-

Pb

IU

Antifreeze protection

The unit will automatically return to normal operation. 

Pd

EU

Coil probe temperature (T3) greater than maxi-

mum limit allowed in cool mode

-

PP

IU

Error due to difference in temperature between 

Twout and Twin not in line with the operating 

mode. The error appears in heat mode if Twout 

is less than Twin for more than 15 minutes 

1.Check the resistance of the 2 temperature probes.

2.Check the position of the 2 probes.

3.The probe connector is disconnected. Reconnect it.

4.One or both probes are faulty; replace them.

5.The four-way valve is blocked. Restart the unit to allow the valve to be released.

6.The four-way valve is broken; replace it. 

UI

: Indoor unit

UE

: Outdoor unit

Содержание IDOLA S 3.2

Страница 1: ...MAINTENANCE AND USER MANUAL EN O FRIEN R E F R I G E R A N T G A S R32 D L Y E C Cod 3541Z090 Rev 05 05 2022 IDOLA S 3 2 WAAL HUNG INDOOR UNITS FOR REVERSIBLE SPLIT HEAT PUMPS WITH DC INVERTER COMPRES...

Страница 2: ...ier The unit and its accessories must be appropriately disposed of in com pliance with current regulations The images given in this manual are a simplified representation of the product In this repres...

Страница 3: ...ostat Low voltage 38 AHS1 AHS2 For additional heat source control GAS BOILER 39 EVU SG Digital inputs for photovoltaic input and smart grid from mains electricity39 Additional temperature probes 39 8...

Страница 4: ...ies made by the supplier which are specifically designed for the equipment and make sure to get installation done by a professional All the activities described in this manual must be carried out by a...

Страница 5: ...charge shall be used Pipework should be protected from physical damage Installation of pipework shall be kept to a minimum If the total refrigerant charge in the system mc is 1 842 kg there are no add...

Страница 6: ...ements VAmin It must be as close as possible to the floor If the ventilation opening starts from the floor the height must be 20mm The bottom of the opening must be situated 100mm from the floor At le...

Страница 7: ...4 0 76 177 3 1 24 0 86 200 3 1 24 0 96 223 3 5 1 45 0 45 105 3 5 1 45 0 55 128 3 5 1 45 0 65 152 3 5 1 45 0 75 175 4 1 66 0 24 57 4 1 66 0 34 80 4 1 66 0 44 103 4 1 66 0 54 127 4 5 1 87 0 03 8 4 5 1 8...

Страница 8: ...equipment falling Make certain that all electrical work is carried out by qualified personnel according to the local laws and regu lations and this manual using a separate circuit Insufficient capacit...

Страница 9: ...ersons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they are supervised or given instruction on using the unit in a safe manner and understand the hazard...

Страница 10: ...sured Places where the units piping and wiring lengths come within the allowable ranges Places where water leaking from the unit cannot cause damage to the location Places where rain can be avoided as...

Страница 11: ...breaker off or pull out the supply cord Otherwise an electric shock and injury may result In order to avoid electric shock or fire make sure that an earth leak detector is installed Be sure the heat...

Страница 12: ...adjacent to the charging area 6 No ignition sources No person carrying out work in relation to a refrigerating system which involves exposing any pipe work that contains or has contained flammable ref...

Страница 13: ...the equipment in use Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere The test apparatus shall be at the correct rating Repla...

Страница 14: ...down refrigerant system if possible e If a vacuum is not possible make a manifold so that refrigerant can be removed from various parts of the system f Make sure that cylinder is situated on the scale...

Страница 15: ...ll required signs are to be maintained and employers should ensure that employees receive suitable and sufficient instruction and training on the meaning of appropriate safety signs and the actions th...

Страница 16: ...tenance operations Reduced inrush current thanks to Inverter technology Compressor with twin rotary DC INVERTER motor equipped with crankcase oil heater positioned on anti vibration rubber supports an...

Страница 17: ...olves a reduction of the maximum compressor frequency and fan speed to reduce the noise emitted and the power absorbed by the unit There are 2 levels of silencing Through time programming it is possib...

Страница 18: ...y to the effective power input of the unit A7W35 source air in 7 C d b 6 C w b system water in 30 C out 35 C A7W45 source air in 7 C d b 6 C w b system water in 40 C out 45 C A7W55 source air in 7 C d...

Страница 19: ...2T 14T 16T UM Efficiency class in heating low temperature produced water 35 C 191 195 205 204 189 185 182 189 185 182 s A class average temperature produced water 55 C 129 138 131 136 135 135 133 135...

Страница 20: ...rculator speed is managed by the hy dronic board in order to insure the correct water temperature difference as in the table below Cooling mode Heating mode For all set points Set point 50 C Set point...

Страница 21: ...unting bracket Front view Bottom view Side view fig 3 dimensional data and connections 8 System outlet 1 M 9 DHW outlet 3 4 M 10 DHW inlet 3 4 M 11 System inlet 1 M 145 Water pressure gauge G Gas line...

Страница 22: ...tlet 10 DHW inlet 11 System inlet 14 Safety valve 36 Automatic air vent valve 56 Expansion vessel 145 Water pressure gauge FL Flow switch G Gas line IBH System electrical heater L Liquid line Pi Water...

Страница 23: ...SV2 Three way valve for heating cooling zone not supplied T1_c Tn_c Cooling request room thermostat not supplied T1_h Tn_h Heating request room thermostat not supplied Ts Temperature probe for solar...

Страница 24: ...ould be lifted by two persons fig 6 7 1 2 Selecting the installation site and minimum operating area for indoor unit WARNING There is flammable refrigerant in the unit and it should be installed in a...

Страница 25: ...at meets the following requirements The installation location is frost free The space around the unit is adequate for servicing see fig 7 The space around the unit allows for sufficient air circulatio...

Страница 26: ...84 1 84 1 84 1 84 1 84 1 84 kg Indoor unit 10 16 16T UM Liquid refrigerant connection 3 8 1 3 8 1 3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 SAE Refrigerant gas connection 5 8 5 8 5 8 5 8 5 8 5 8 5 8 5 8 5 8 5 8...

Страница 27: ...r poisonous gas 7 5 Refrigerant connections Comply with the following indications when connecting the refrigerant pipes Make sure that the refrigerant pipes can withstand the refrigerant maximum press...

Страница 28: ...s are the right shape Wipe off the liquid soap with a rag Reduce the pressure of the nitrogen in the circuit by loosening the charge pipe from the bottle Having reduced the pressure disconnect the nit...

Страница 29: ...evice is to be operated regularly to remove lime deposits and to verify that it is not blocked Before installation flush all the pipes of the system thoroughly to remove any residuals or impurities th...

Страница 30: ...s must be made in accordance with the outlook diagram delivered with the unit with respect to the water intake and water outlet If air moisture or dust gets in the water circuit problems may occur The...

Страница 31: ...0 240V 50 Hz 220 240V 50 Hz 380 415 3 N PE 50 Hz Maximum input current A 13 13 10 Automatic switch A 16 16 16 Power cable section mm2 3x1 5 3x1 5 5x1 5 The customer must install the automatic circuit...

Страница 32: ...fety regulations Have the efficiency and suitability of the earthing system checked by professionally qualified personnel the manu facturer is not responsible for any damage caused by lack of earthing...

Страница 33: ...wards fig 19 remove the metal sheet of the rear cover detail 3 fig 19 secured with 2 screws detail 4 fig 19 NB The rear fastening bracket can be removed detail 2 fig 17 by removing the screw detail 2b...

Страница 34: ...rigerant side of the indoor unit heating mode B T2B Port for temperature probe on gas refrigerant side of the indoor unit heating mode B TW_in Port for temperature probe of inlet water of plate exchan...

Страница 35: ...2 16 N 14 IBH1 Indoor back up system electric heater 1 B 17 N 18 N SV3 mixer valve 3 way valve zone 2 2 19 3ON 20 3OFF 25 CN2 TBH_FB Port for automatic circulation TBH switch in short circuit by defau...

Страница 36: ...1 A2 CN11 25 26 1 2 3 4 5 6 7 8 9 10 CN7 CN30 27 28 29 30 31 32 9 21 Pumpc zone2 pump fig 24 P_d DHW recirculation pump Power supply A1 A2 CN11 25 26 1 2 3 4 5 6 7 8 9 10 CN7 CN30 27 28 29 30 31 32 12...

Страница 37: ...fig 30 Room thermostat method B one zone control To activate this function set the service parameter 6 1 Room thermostat 2 one zone refer to 9 2 Service parameters table on page 51 B 1 When unit detec...

Страница 38: ...2 1 9 0 1 18 8 7 5 4 2 2 2 3 2 1 2 13 3 4 6 20 14 15 17 19 16 21 6 8 9 10 5 4 3 2 1 CN4 CN22 CN5 S3 DIS1 CN24 CN1 CN2 CN6 CN8 CN13 CN15 CN16 CN18 CN28 S2 CN42 CN21 S1 S4 CN11 CN7 CN17 CN19 CN30 CN35...

Страница 39: ...HW request Normal operation In this case the system works normally according to the set parameters Smart grid operation This operation is usually dependent of a smart grid request by the mains electri...

Страница 40: ...off short press switches of DHW or Z1 or Z2 de pending on the selection pressure 5 sec switches off everything DHW Z1 Z2 SW6 UP VALUE Increases DHW Z1 Z2 set temperature Increases the parameter value...

Страница 41: ...Delivery set point single zone without Z1 Z2 on the side Delivery set point zone 1 if Z1 on the side Delivery set point zone 2 if Z2 on the side If it is configured as single zone only Z1 Z2 will not...

Страница 42: ...press the SW6 SW7 buttons to change the set point confirm the modified value with the SW3 button Zone Z1 set point Type of terminal selected Heat setpoint min max Cool setpoint min max FLH radiant flo...

Страница 43: ...NO NO Event 2 Time Start time hh mm 00 00 23 59 1 min hh mm 00 00 Event 3 Temperature Water temperature setpoint 5 25 1 C 8 Event 4 Event 5 Event 6 Friday Event 1 Enable y n Enables the Eevent YES NO...

Страница 44: ...0 00 Fast Dhw state Enable Y N yes no activates all sources to heat dhw quickly with the sati sfied setpoint the function is automatically disabled and remains disabled None ON OFF None Tank Heater st...

Страница 45: ...f to setup if heat mode is On Off during the holiday ON OFF ON From Date first day of holiday 01 01 2000 01 06 2099 01 01 2021 Until Date last day of holiday 01 01 2000 01 06 2099 01 01 2021 Backup He...

Страница 46: ...measured by probe Tw_out 1 C Tw_I Plate Inl Temp Water temperature measured by probe Tw_in 1 C Tbt1 Buf Tank Up Temp Water temperature measured by probe Tbt1 1 C Tbt12 Buf Tank Low T not used C Tsola...

Страница 47: ...ay Event 1 Enabled y n Enable the event Event 2 Time Start time hh mm Event 3 Temperature Water temperature setpoint Event 4 Event 5 Event 6 The temperature setting remains active until the next enabl...

Страница 48: ...will work for the plant and with the TBH electric heater for DHW If the temperature sensor T5 of the DHW tank is faulty the TBH electric heater cannot work DHW pump Dhw Pump Circ Men Hp Dhw settings...

Страница 49: ...force the activation of the electric system heater and make the heating of the water sent to the heating system more speedy Bckp Heat On Off Enabling and disabling of back up electric heater 1 ON 2 O...

Страница 50: ...control 1 1 9kW IBH three stage control OFF OFF 3 4 0 0 without IBH and AHS 1 0 with IBH 0 1 with AHS for heating mode 1 1 with AHS for heating mode and DHW mode ON OFF DIP switch ON 1 OFF 0 Factory...

Страница 51: ...um time for the antilegionella function 90 300 5 min 210 1 17 T_Dhwhp_Restrict System maximum operating time with parameter Dhw Priority Time Set YES 10 600 5 min 30 1 18 T_Dhwhp_Max DHW mode maximum...

Страница 52: ...n of the back up system electric heater 15 120 5 MIN 30 7 3 T4_IBH_ON Maximum external air temperature below which the back up system electric heater can be activated 15 10 1 C 5 7 4 dT1_AHS_ON The te...

Страница 53: ...ture probe Tbt1 Yes No No 15 5 Tbt2 Reserved No 15 7 Solar Input SOLAR ENABLE Enables solar input Yes No No IN SOLAR Type of solar input Tsolar to enable the Tsolar solar panel probe temperature SL1SL...

Страница 54: ...3 7 52 5 51 6 50 6 50 0 1 Fancoil or Radiators H1 53 0 52 4 51 7 50 5 49 6 48 6 48 0 2 52 0 51 4 50 7 49 5 48 6 47 6 47 0 3 50 0 49 4 48 7 47 5 46 6 45 6 45 0 4 48 0 47 4 46 7 45 5 44 6 43 6 43 0 5 45...

Страница 55: ...radiator C2 21 0 21 0 19 0 19 0 18 0 18 0 17 0 17 0 2 22 0 22 0 20 0 20 0 19 0 19 0 17 0 17 0 3 23 0 23 0 21 0 21 0 19 0 19 0 18 0 18 0 4 24 0 24 0 21 0 21 0 20 0 20 0 18 0 18 0 5 24 0 24 0 22 0 22 0...

Страница 56: ...water pressure must be 1 bar with cold system water Make sure that the expansion vessel is not broken Check that the pressure drop in the hydraulic circuit is not too high for the pump The volume of...

Страница 57: ...eter on the maximum value Check that the Dhw Priority is 1 DHW priority enabled If the parameter Dhw Priority 0 set the t_DHWHP_RESTRICT parameter on the minimum value Set dT1SH to 2 C Enable the DHW...

Страница 58: ...waterproof adhesive tape 4 Faulty probe replace it E5 UE Temperature probe fault Refrigerant leaking from coil T3 Check the probe resistance 2 The probe connector is disconnected Reconnect it 3 The pr...

Страница 59: ...ed Reconnect it 3 The probe connector is wet Remove the water and dry the connector Apply waterproof adhesive tape 4 Faulty probe replace it H3 IU Refrigerant gas temperature probe fault T2B 1 Check t...

Страница 60: ...verter module protection L1 EU Protection for low voltage on DC bus L2 EU Protection for high voltage on DC bus L4 EU MCE error L5 EU Zero speed protection L7 EU Phase sequence error L8 EU Frequency v...

Страница 61: ...2 Setting to be done during the initial check of the product For the correct functioning of the system it is mandatory to make the correct settings that depend on the type on the system served by the...

Страница 62: ...delivery pipe Burns Contact with pipes and or compressor Avoid contact by wearing protective gloves Drain pipe and coil Explosion Excessive pressure Switch off the machine check the high pressure swit...

Страница 63: ...r Modbus BMS VALVES PUMPS C DISPLAY CB LPS Circuit Breaker must be installed to the Power Supply of the unit Leakage Protection Switch must be installed to the Power Supply of the unit Probe S ST T5 S...

Страница 64: ...er must be installed to the Power Supply of the unit Leakage Protection Switch must be installed to the Power Supply of the unit 25 C 45 C L1 B L2 A L2 B N a IBH1 a R2 IBH1 L3 B T1 T2 T3 1 2 3 TH IBH1...

Страница 65: ...r probe E11 Stop valve gas E12 Stop valve liquid E13 High pressure switch E14 Lowe pressure switch E15 Pressure sensor E16 Capillary E17 Extraction temperature probe INDOOR UNIT 8 System outlet 9 DHW...

Страница 66: ......

Страница 67: ......

Страница 68: ...borghini Caloreclima www lamborghinicalor it un marchio commerciale di FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona Italy tel 39 045 6139411 fax 39 045 6100933 www ferroli com Made in Ita...

Отзывы: