52
EN
Cod. 3541Z090 - Rev. 05 - 05/2022
IDOLA S 3.2
Menu
Level 1
Menu
Level 2
Menu
Level 3
Menu
Level 4
Description
Lower
limit
Upper
limit
Remedy
Unit of
measure-
ment
Default
value
For Serviceman 3 Heat Mode
Setting
3.1 Heat Mode
Enables or disables the heating mode
Yes
No
/
/
Yes
3.2 T_T4_Fresh_H
The set point update time calculated by the
climatic curve for the heating mode
0.5
6
0.5
h
0.5
3.3 T4Hmax
The maximum external air temperature to which
the heat pump can operate in heating mode
20
35
1
°C
25
3.4 T4Hmin
The minimum external air temperature to which
the heat pump can operate in heating mode
-25
30
1
°C
-15
3.5 Dt1Sh
Hysteresis set point for restarting the heat pump
in heating mode
2
20
1
°C
5
3.6 Reserved
Reserved
-
-
-
-
-
3.7 T_Interval_H
Time between shut-down and start-up of the
compressor in heating mode
5
60
1
min
10
3.8 T1Seth1
Set point 1 of climatic curve no. 9 for heating
mode.
25
65
1
°C
35
3.9 T1Seth2
Set point 2 of climatic curve no. 9 for heating
mode.
25
65
1
°C
28
3.10 T4H1
The external air temperature 1 of the climatic
curve no. 9 for the heating mode.
-25
35
1
°C
-5
3.11 T4H2
The external air temperature 2 of the climatic
curve no. 9 for the heating mode.
-25
35
1
°C
7
3.12 Zone1 H-Emission
The type of zone 1 terminal for cooling mode:
FCU (fancoil): RAD. (Radiator): FLH (floor
heating)
FCU/
RAD
FLH
/
/
FCU/
RAD
3.13 Zone2 H-Emission
The type of zone 2 terminal for cooling mode:
FCU (fancoil), RAD (radiator), FLH (floor heating)
FCU/
RAD
FLH
/
/
FLH
3.14 T_Delay_Pump
Delay between pump activation and subsequent
compressor activation
2.0
20.0
0.5
min
2.0
For Serviceman 5 Temp. Type
Setting
5.1 Water Flow Temp.
Reserved
Yes
No
/
/
Yes
5.2 Room Temp.
Reserved
Yes
No
/
/
No
5.3 Double Zone
Double zone
Enables/disables control of 2 zones
Yes
No
/
/
No
For Serviceman
6 Room
Thermostat
6.1Room Thermostat
none / mode setting /one
zone / double zone
Select the type of control on the thermostat digital
input (none, mode setting, one zone, double
zone)
None / Mode Set / One Zone / Double Zone
None
For Serviceman 7 Other Heating
Source
7.1 dT1_IBH_ON
The temperature difference between T1S and T1
for starting the back-up system electric heater.
2
10
1
°C
5
7.2 t_IBH_DELAY
Compressor operating time before the activation
of the back-up system electric heater
15
120
5
MIN
30
7.3 T4_IBH_ON
Maximum external air temperature below which
the back-up system electric heater can be
activated
-15
10
1
°C
-5
7.4 dT1_AHS_ON
The temperature difference between T1S and
T1 for switching on the additional heating source
(gas boiler)
2
20
1
°C
5
7.5 t_AHS_DELAY
Compressor operating time before activating the
additional heating source (gas boiler)
5
120
5
MIN
30
7.6 T4_AHS_ON
Maximum external air temperature below which
the additional heating source (gas boiler) can be
activated
-15
30
1
°C
-5
7.7 IBH LOCATE
Pipe Loop=0; Buffer
Tank=1
Installation position of the back-up system
electric heater IBH
PIPE LOOP = 0 if the system electric heater is
installed in series with the heat pump;
BUFFER TANK = 1 if the system electric heater
is installed on the system tank
0
1
0
/
0
For Serviceman
8 Holiday
Setting
8.1 T1S H.A. H
The target water output temperature for heating
the room in holiday mode
20
25
1
°C
25
8.2 T5S H.A. DHW
DHW water heater temperature set point in
holiday mode
20
25
1
°C
25
For Serviceman
10 Restore
Factory Settings
10, 1 Restore Factory
Settings
Restore Factory Settings
Y
N
/
/
N
For Serviceman
11 Test Run
11.1 Test Run Enable
TEST RUN ENABLE 0 = OFF 1 = ON - to enable
the menu “11.2 Trail run steps”
OFF
ON
/
/
OFF
11.2 Trail run steps
Point Check = to activate the menu “11.3 Point Check”
Air purge = ON - to activate the air bleed
Water pump = ON - to activate the water pump
Cooling = ON - to activate the cooling mode
Heating = ON -to activate the heating mode
Dhw = ON - to activate the DHW mode
Point Check / Air purge / Water pump / Cooling
/ Heating / Dhw
Point
Check
11.3 Point Check
3way-valve 1
TEST ON-OFF
Allows you to run a functional test on single loads, individually
forcing the activation and subsequent switching off.
Also allows you to temporarily force the system in specific
function modes for the test (air bleed, recirculation pump
running, etc.).
The switching on/off of each function is always done
manually.
It is only possible to enable/disable one function at a time; it is
not allowed at the same time.
If one function is active and you exit the Test Run menu while
it is active, the function will automatically switch off.
OFF
ON
/
/
OFF
3way-valve 2
OFF
ON
/
/
OFF
PUMPS
OFF
ON
/
/
OFF
PUMP
OFF
ON
/
/
OFF
PUMPC
OFF
ON
/
/
OFF
PUMPSOLAR
OFF
ON
/
/
OFF
PUMPDHW
OFF
ON
/
/
OFF
INNER BACKUP HEATER
OFF
ON
/
/
OFF
TANK HEATER
OFF
ON
/
/
OFF
3WAY-VALVE 3
OFF
ON
/
/
OFF