40
9.7.5 Remove the switch box cover
NOTE
Unit
4kW
6kW
8kW
10kW
12kW
14kW
16kW 12kW 3-PH 14kW 3-PH 16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
18
18
19
19
30
30
30
14
14
14
Wiring size(mm
2
)
4.0
4.0
4.0
4.0
6.0
6.0
6.0
2.5
2.5
2.5
MCA : Min. Circuit Amps. (A)
TOCA : Total Over-current Amps. (A)
MFA : Max. Fuse Amps. (A)
MSC : Max. Starting Amps. (A)
RLA : In nominal cooling or heating test condition
,
the input Amps of compressor where MAX. Hz
can operate Rated Load Amps. (A)
KW : Rated Motor Output
FLA : Full Load Amps. (A)
Unit
8kW
10kW
12kW
14kW
16kW 12kW 3-PH 14kW 3-PH 16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
32
32
43
43
43
27
27
27
Wiring size(mm
2
)
8.0
8.0
10.0
10.0
10.0
4.0
4.0
4.0
1-phase 8-16kW and 3-phase 12-16kW standard with backup heater 9kW(3-phase)
Unit
4kW
6kW
8kW
10kW
12kW
14kW
16kW 12kW 3-PH 14kW 3-PH 16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
31
31
32
32
43
43
43
27
27
27
Wiring size(mm
2
)
6.0
6.0
8.0
8.0
10.0
10.0
10.0
4.0
4.0
4.0
1-phase 4-16kW and 3-phase 12-16kW standard with backup heater 3kW (1-phase)
1-phase 4-16kW standard and 3-phase 12-16kW standard
UNIT POWER SUPPLY
1-phase
L
N
L N
LPS
F
USE
UNIT POWER SUPPLY
3-phase
LPS
F
USE
L1
N
L2 L3
L3
N
L2
L1
UNIT POWER SUPPLY
3-phase
LPS
F
USE
L1
N
L2 L3
L3
N
L2
L1
UNIT POWER SUPPLY
1-phase
L N
LPS
F
USE
The ground fault circuit interrupter must be 1 high-speed type of 30mA(<0.1s). Please use 3-core shielded wire.
The default of backup heater is option 3 (for 9kW backup heater). If 3kW or 6kW backup heater is needed, please
ask professional installer to change the Dip switch of S1 to option 1(for 3kW backup heater) or option 2(for 6kW backup
heater), refer to 10.1.1 FUNCTION SETTING.
Stated values are maximum values (see electrical data for exact values).
EN
IDOLA M 3.2
04÷16T
CAUTION
34
Ethylene Glycol and Propylene Glycol are TOXIC
WARNING
NOTE
During filling, it might not be possible to remove all air in the system. Remaining air will be removed through the
automatic air purge valves during the first operating hours of the system. Topping up the water afterwards might be
required.
The water pressure will vary depending on the water temperature (higher pressure at higher water temperature).
However, at all times water pressure should remain above 0.3 bar to avoid air entering the circuit.
The unit might drain-off too much water through the pressure relief valve.
Water quality should be complied with EN 98/83 EC Directives.
Detailed water quality condition can be found in EN 98/83 EC Directives.
Connect the water supply to the filling valve and open the valve.
Make sure the automatic air purge valve is open (at least 2 turns).
Fill with water pressure of approximately 2.0 bar. Remove air in the circuit as much as possible using the air purge
valves. Air in the water circuit could lead to malfunction of the backup electric heater.
9.5 Filling water
Do not fasten the black plastic cover on
the vent valve at the topside of the unit
when the system is running. Open air
purge valve, turn anticlockWise at least
2 full turns to release air from the
system.
CounterclockWise rotation, remove the flow switch.
Drying the flow switch completely.
When the unit is not running for a long time, make sure the unit is powered on all the time. If you want to cut off the
power, the water in the system pipe needs to be drained clean to avoid the unit and pipeline system being damaged by
freezing. Also the power of the unit needs to be cut off after water in the system is drained off.
Cod. 3QE47850 - Rev. 00 - 03/2022