23
GB
Table 1
Press the “operation mode selection – M button (detail.2 - fig.1) for 5 seconds to exit the
menu.
Service parameters Menu
Press the programming button “P”(detail 5-fig.1) for 10 seconds to access the parameters
menu. The parameter “t01” is dislayed: idintified by the message SET 01.
Press the button “P” ”(detail 5-fig.1) to scroll the list of parameters.
To modify the value of a parameter just press the + and – buttons (detail 4 and 6- fig.1: the
change will be automatically stored. After modifying the parameter, It is necessary to wait 3
seconds: the data flashes and is stored.
Table 2
* Only parameter display
** 0-30 = Optimal operating condition
Press the programming button “P” (part. 5 - fig. 1) for 10 seconds to exit the menu.
Parameter Description
Range
Default 3.4 P
Default 5.5 P
t01
Pellet loading function
0=Disabled
1=Enabled
0=Disabled
0=Disabled
t02
Delivery probe
0=Disabled
1=Enabled
1=Enabled
1=Enabled
t03
Fan setpoint in Lighting
0-200 Pa
51 Pa
51 Pa
t04
Auger activation time in Lighting
0-100 (1=4sec)
8
8
t05
Adjustment calculation timer (only with Modulating
burner operation with delivery Probe)
0-100 seconds
5 seconds
5 seconds
t06
Ramp function timer
0-100 seconds
100 seconds
100 seconds
t07
Period /actdeactivation time) with auger opera
-
ting (from Power 1 to Power 5)
0-50 seconds
15 seconds
12 seconds
t08
Fan setpoint at Power 1
0-200 Pa
51 Pa
60 Pa
t09
Auger activation time at Power1
0-100 (100=10s)
28
30
t10
Fan setpoint at Power 2
0-200 Pa
74 Pa
105 Pa
t11
Auger activation time at Power 2
0-100 (100=10s)
38
40
t12
Fan setpoint at Power 3
0-200 Pa
120 Pa
130 Pa
t13
Auger activation time at Power 3
0-100 (100=10s)
46
46
t14
Fan setpoint at Power 4
0-200 Pa
150 Pa
160 Pa
t15
Auger activation time at Power 4
0-100 (100=10s)
53
54
t16
Fan setpoint at Power 5
0-200 Pa
170 Pa
190 Pa
t17
Auger activation time at Power 5
0-100 (100=10s)
56
70
t18
Burner operation selection (Only with Delivery Probe)
0=On/Off
1=modulating
0
0
t19
Post –Ventilation time 2
0-100 (100=10s)
99
99
t20 *
Voltage photoresistor
0-30 (50=5Vdc)**
--
--
Parameter Description
Range
Default 3.4 P
Default 5.5 P
u01
Delivery setpoint adjustement
30 – 80 °C
80°C
80°C
u02
Burner max. power
1 - 5
3
3
u03
Burner operation methods
0 - 2
0
0