Lamborghini Caloreclima ECO 5.5 P Скачать руководство пользователя страница 7

23

GB

Table 1

Press the “operation mode selection – M button (detail.2 - fig.1) for 5 seconds to exit  the 

menu.

Service parameters Menu

Press  the  programming  button  “P”(detail  5-fig.1)  for  10  seconds  to  access  the  parameters 

menu. The parameter “t01” is dislayed: idintified by the message SET 01.

Press the button “P” ”(detail 5-fig.1) to scroll the list of parameters.

To modify the value of a parameter just press the + and – buttons (detail 4 and 6- fig.1: the 

change will be automatically stored. After modifying the parameter, It is necessary to wait 3 

seconds: the data flashes and is stored.

Table 2

* Only parameter display

** 0-30 = Optimal operating condition

Press the programming button “P” (part. 5 - fig. 1) for 10 seconds to exit the menu.

Parameter Description

Range

Default 3.4 P

Default 5.5 P

t01

Pellet loading function

0=Disabled

1=Enabled

0=Disabled

0=Disabled

t02

Delivery probe

0=Disabled

1=Enabled

1=Enabled

1=Enabled

t03

Fan setpoint in Lighting

0-200 Pa

51 Pa

51 Pa

t04

Auger activation time in Lighting

0-100 (1=4sec)

8

8

t05

Adjustment calculation timer (only with Modulating 

burner operation with delivery Probe)

0-100 seconds

5 seconds

5 seconds

t06

Ramp function timer

0-100 seconds

100 seconds

100 seconds

t07

Period /actdeactivation time) with auger opera

-

ting (from Power 1 to Power 5)

0-50 seconds

15 seconds

12 seconds

t08

Fan setpoint at Power 1

0-200 Pa

51 Pa

60 Pa

t09

Auger activation time at Power1

0-100 (100=10s)

28

30

t10

Fan setpoint at Power 2

0-200 Pa

74 Pa

105 Pa

t11

Auger activation time at Power 2

0-100 (100=10s)

38

40

t12

Fan setpoint at Power 3

0-200 Pa

120 Pa

130 Pa

t13

Auger activation time at Power 3

0-100 (100=10s)

46

46

t14

Fan setpoint at Power 4

0-200 Pa

150 Pa

160 Pa

t15

Auger activation time at Power 4

0-100 (100=10s)

53

54

t16

Fan setpoint at Power 5

0-200 Pa

170 Pa

190 Pa

t17

Auger activation time at Power 5

0-100 (100=10s)

56

70

t18

Burner operation selection (Only with Delivery Probe)

0=On/Off

1=modulating

0

0

t19

Post –Ventilation time 2

0-100 (100=10s)

99

99

t20 *

Voltage photoresistor

0-30 (50=5Vdc)**

--

--

Parameter Description

Range

Default 3.4 P

Default 5.5 P

u01

Delivery setpoint adjustement

30 – 80 °C

80°C

80°C

u02

Burner max. power

1 - 5

3

3

u03

Burner operation methods

0 - 2

0

0

Содержание ECO 5.5 P

Страница 1: ...01 PROIZVOD SA SERTIFIKATOM ISO 9001 UNI EN ISO 9001 ECO 3 4 P ECO 5 5 P Bruciatore a pellet Pellet burner Plamenik na pelete Gorionik na pelete Libretto uso e manutenzione Installation and maintenanc...

Страница 2: ...Installation and maintenance must be carried out by professionaly qualified personnel in compilance with current regulations and the manufaturer s instructions Incorrect installation or poor maintena...

Страница 3: ...internal clock or contact C Burner management Second internal clock or contact OPERATING INSTRUCTIONS Fig 1 Control panel Fig 1 Method A Methods B and C 1 Day time setting button 2 Operation mode sel...

Страница 4: ...the unit During the first 10 seconds the display shows The software version of the user interface and the controller fig 3 A nOCU fig 5 may appear for a couple of seconds fig 3 B C Adjustements Settig...

Страница 5: ...not show the ON icon or CLOCK icon The bur ner is off The set weekly programme is by passed Preset factory set weekly programme 06 30 08 30 12 00 12 00 16 30 22 30 The weekly programme is present with...

Страница 6: ...5 8 1 Use the and buttons part 4 e 6 fig 1 to modify the start of the 3rd ON time band example 16 00 Press the Programming button P detail 5 fig 1 9 22 30 on Radiator flash 6 9 1 Use the and buttons p...

Страница 7: ...c 8 8 t05 Adjustment calculation timer only with Modulating burner operation with delivery Probe 0 100 seconds 5 seconds 5 seconds t06 Ramp function timer 0 100 seconds 100 seconds 100 seconds t07 Per...

Страница 8: ...off operation It is necessary to set the maximum power of the burner as a function of the boiler s power see table 3 Table 3 General instructions This unit must only be used for its inteded purpose Th...

Страница 9: ...tile substances which drawn by the fan can obstruct yhe pipes inside the burner or the combustion head The room must be dry and not exposed to rain snow or frost Fix the burner to the door Make the el...

Страница 10: ...mage caused by failure to earth the system Also make sure the electrical system is adequate for the maximun power absobed by the unit as specified on the boiler dataplate Make sure torespect the polar...

Страница 11: ...d attempt was not sufficient repeat the previous sequence from point 4 to start the third and last attempt 9 In order to do another 3 attempts switch the power to the unit off and then on again 10 Aft...

Страница 12: ...in the boiler with the preliminary settings indicated above Make sure the boiler and system are filled with water or diathermic oil the plumbing circuit valves are open and that the flue is free and...

Страница 13: ...r at least 10 minutes operation and check of correct setting Opening of casing and burner disassembly Before carrying out any checking oe cleaning inside the burner disconnect the power to the burner...

Страница 14: ...tainer empty auger cable broken or disconnec ted faulty igniter resistance combustion head dirty pellet feed duct blocked fill the container with pellets restore the connection replace and empty the h...

Страница 15: ...nnectly plug 5 User interface 7 Photoresistance General view and main components 8 Thermostat 85 C 9 Burner loading tube 10 Motor 11 Fan 12 Nozzle 13 Griglia 60 4 5 A B C D E F G H L M A B C D E F G H...

Страница 16: ...el delivery kg h 2 9 6 3 Electrical protection rating IP X0D X0D Power voltage frequency V Hz 230 50 230 50 Electrical absorption motor W 50 70 Igniter rated power W 300 300 Empty weight kg 11 19 Hopp...

Страница 17: ...33 GB FR IU MB TST CA CM PA PS SB STR TC Important Before connecting the rquest contact remove the jumper on the connection plug...

Страница 18: ...359947 The illustrations and data given are indicative and not binding Lamborghini Calor reserves the right to make all modifications it deems appropriate for improvement of the product without forew...

Отзывы: