cod. 3541T620 - Rev. 05 - 04/2022
146
EN
DORA
90 LT - 120 LT
fig. 44- Safety thermostat reset
ATTENTION
The intervention of the safety
thermostat may occur due to a
fault in the control board or the
absence of water in the boiler
tank.
NB!: The intervention of the thermostat ex-
cludes the operation of the electrical resist-
ance but not the heat pump system within the
allowed operating limits.
ATTENTION
If the operator is unable to elim-
inate the fault, switch off the
equipment and contact the Tech-
nical Assistance Service, com-
municating the model of the
product purchased.
7.3
CHECK/REPLACEMENT OF THE
SACRIFICIAL ANODE
The integrity of the Mg anodes must be checked at least
once every two years (once a year is recommended). The
check should be carried out by a qualified technician.
The magnesium anode (Mg), also known as an "sacrificial" an-
ode, prevents any eddy currents generated inside the boiler
from triggering surface corrosion.
Magnesium is, in fact, a less noble metal than the material lin-
ing the inside of the boiler, therefore, it attracts the negative
charges first that are formed by heating the water, and is con-
sumed. The anode, therefore, “sacrifices” itself and corrodes
instead of the boiler tank. The boiler has two anodes, one fitted
in the lower part of the tank and one fitted in the upper part of
the tank (area more subject to corrosion).
Before carrying out the check, you must:
• Close the cold water inlet.
• Proceed with emptying the boiler (see par. “7.4 EMPTYING
THE BOILER”).
• Remove the bottom cover 1.
• Disconnect the heating element safety thermostat electri-
cal connection from the power board and remove the water
NTC probes from the dedicated pipe in the element flange.
• Remove the flange by unscrewing the bolts 3. The corrosion
of the anode 4 can then be checked; if it affects more than
2/3 of the anode surface, proceed with replacement.
fig. 45
fig. 46
The flange has a special gasket which must be replaced if the
anode is checked or replaced.
7.4
EMPTYING THE BOILER
If not in use, especially in case of low temperatures, it is advis-
able to drain the water inside the boiler. For the equipment in
question, just open the drain cock as per the example hydrau-
lic connections chap. “6.7 HYDRAULIC CONNECTIONS” on
page 135 (see fig. 35).
NB!: In case of low temperatures, remember
to empty the system to avoid freezing.
Содержание DORA 120 LT
Страница 2: ...IT 3 ES 53 EN 105...
Страница 29: ...29 cod 3541T620 Rev 05 04 2022 IT DORA 90 LT 120 LT fig 21 fig 22 5 2 DATI DIMENSIONALI fig 23 fig 24...
Страница 79: ...79 c d 3541T620 Rev 05 04 2022 ES DORA 90 LT 120 LT fig 21 fig 22 5 2 DATOS DIMENSIONALES fig 23 fig 24...
Страница 102: ...c d 3541T620 Rev 05 04 2022 102 ES DORA 90 LT 120 LT...
Страница 129: ...129 cod 3541T620 Rev 05 04 2022 EN DORA 90 LT 120 LT fig 21 fig 22 5 2 DIMENSIONAL DATA fig 23 fig 24...